Operating instructions for EE310 Humidity / Temperature Transmitter
3.2.9 Connection diagram for alarm outputs AM6
NO
NC
C
NC
6
NO
4
C
5
NC
3
NO
1
C
2
NO
NC
C
Standard
Inverted
REL 1
REL 2
RELA
Y 2
RELA
Y 1
Wire size:
18-16AWG
Type:
CU
Terminal torque
USA:
7 Lb In.
CANADA: 0.8 Nm
Note:
½” Liquid-Tight Flexible Nonmetallic Conduit Type B (FNMC-B) is installed. Cable used for installation
shall be suitable flexible listed cord/cable in accordance with NEC. Local regulation for installation must
be observed.
Model
Supply Input
Terminals
Voltage/Frequency
EE310 with option AM6
Relay 1:
Max. switch load: 250 Vac / 6 A and 28 Vdc / 6 A
Min. switch load: 12 Vacdc / 100 mA
C (5) -
NO (4)
C (5) -
NC (6)
EE310 with option AM6
Relay 2:
Max. switch load: 250 Vac / 6 A and 28 Vdc / 6 A
Min. switch load: 12 Vacdc / 100 mA
C (2) -
NO (1)
C (2) -
NC (3)
V+
GND
GND
OUT 1
OUT 2
GND RS485
RS485 A (=D+)
RS485 B (=D-)
V
mA
8 - 35 V DC
12 - 30 V AC
1
2
3
4
5
6
7
8
Modbus RTU
(galvanically isolated)
Analogue outputs
Supply
V
mA
Wire size:
30-16AWG
Type:
CU
Terminal torque
USA:
6 Lb In.
CANADA: 0.7 Nm
Model
Supply Input
Terminals
Voltage/Frequency
EE310 with option AM6
Indoor use:
12 to 30Vac, 50/60Hz (Class 2 supply)
8-35Vdc (LPS)
Outdoor use:
12 to 16Vac, 50/60Hz (Class 2 supply)
8-35Vdc (LPS)
V+ (1) –
GND (2)