Operating instructions for EE310 Humidity / Temperature Transmitter
The probe shall be horizontal or point downwards.
Fig. 15
Mounting of model EE310-T2
For UL Type 4 the back of the device (probe feedthrough) must be protected from direct water impact.
3.3.3 T5: Remote probe up to 180 °C
(356 °F)
EE310-
T5
are transmitters with remote probe.
For mounting template of enclosure see chapter
3.1 Mechanical installation /
Fig. 4 Dimensions and mounting template of polycarbonate enclosure in mm (inch)
.
T working range probe:
-40...+180 °C
(-40...176 °F)
cable:
-40...+150
(-40...302 °F)
electronics:
-40...+60 °C
(-40...140 °F)
-20...+50
°C
(-4...122 °F)
(with display)
Mounting the remote sensing probe of EE310-T5
For mounting the probe into a separation wall use the stainless steel mounting flange (see
chapter
8 Replacement parts / Accessories
). The immersion depth is adjustable. The probe shall be
horizontal.
In case of mounting into a separation wall, it is of paramount importance for accurate measurement to
avoid T gradients along the probe. In case of large T difference between the two sides of the separa-
tion wall, it is highly recommended to insert the probe completely (up to the cable outlet) into the wall.
Should this not be possible, place a thermal isolation layer on the part of the probe outside the wall (on
the cable side).
The stainless steel mounting flange is not appropriate for pressure tight mounting. For pressure tight
requirements use EE310-T10.
For probe hanging onto its cable from the ceiling in applications where condensation is likely to happen
it is important to avoid condense water getting from the cable to the probe and into the sensing head.
For this use the drip water protection.