Operating instructions for EE310 Humidity / Temperature Transmitter

Outputs

Model

Type

Ratings

Terminals

EE310 with option AM3

Out 1

0-1V 

0-5V 

0-10V

0-20mA 

4-20mA

(SELV Limited Energy source)

Plug pin

Out 1 (1) – 

GND (5)

Out 2

0-1V

0-5V

0-10V

0-20mA

4-20mA

(SELV Limited Energy source)

Plug pin

Out 2 (4) – 

GND (5)

Model

Type

Ratings

Terminals

EE310 with options 

AM3 and J3

Modbus RTU

0-5V

 (SELV Limited Energy source)

RS485 A (=D+) (7) – 

RS485 B (=D-) (8) – 

GND RS485 (6)

Tab. 8 

M12 conector analogue and digital output

3.2.7  Connection digram for integrated power supply module AM5

Wire size:

 30-16AWG

Type:

 CU

Terminal torque

USA: 

7 Lb In.

CANADA:  0.8 Nm

Fig. 13 

Option AM5 with liquid-tight conduit fittings

Note:

½” Liquid-Tight Flexible Nonmetallic Conduit Type B (FNMC-B) is installed. Cable used for installation 

shall be suitable flexible listed cord/cable in accordance with NEC. Local regulation for installation must 

be observed

V+

GND

GND

OUT 1

OUT 2

GND RS485

RS485 A (=D+)

RS485 B (=D-)

V

mA

8 - 35 V DC

12 - 30 V AC

1

2

3

4

5

6

7

8

Modbus RTU
(galvanically isolated)

Analogue outputs

Supply

V

mA

Wire size:

 30-16AWG

Type:

 CU

Terminal torque

USA: 

6 Lb In.

CANADA:  0.7 Nm

Содержание EE310

Страница 1: ...BA_EE310_UL V1 0 Technical data subject to change 194720 Operation manual EE310 Humidity Temperature Transmitter...

Страница 2: ...imits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequenc...

Страница 3: ...to 180 C 356 F 20 3 3 4 T10 T8 Remote probe up to 180 C 356 F 21 3 3 5 T10 Installation of the probe directly in the process with sliding fitting up to 20 bar 290 psi 22 3 3 6 T10 Installation of the...

Страница 4: ...d The replacement of the filter cap shall be done with utmost care not to touch the sensors Installation electrical connection maintenance and commissioning shall be performed by qualified staff only...

Страница 5: ...four measurands simultaneously and offers exten sive error diagnostics The integrated data logging function saves all measured and calculated values to the internal memory The data can be displayed as...

Страница 6: ...dels EE310 is available for wall surface or duct mount as well as with various remote probes The remote probes can be employed up to 180 C 356 F and 20 bar 300 psi T1 Wall or surface mounting T2 Duct...

Страница 7: ...4 09 71 2 80 5 1 0 20 166 6 54 180 7 09 153 6 02 54 2 13 14 0 55 166 6 54 5 1 0 20 7 0 28 Fig 4 Dimensions and mounting template of polycarbonate enclosure in mm inch The four housing screws shall be...

Страница 8: ...on according to NAMUR NE43 In the case of an error the output signal will freeze at 21 mA or 11 V respectively Note By default the error indication is disabled When changing one of the analogue output...

Страница 9: ...c 50 60Hz Class 2 supply 8 35Vdc LPS V 1 GND 2 Outputs Model Type Ratings Terminals EE310 Out 1 0 1V 0 5V 0 10V 0 20mA 4 20mA SELV Limited Energy source Out 1 4 GND 3 Out 2 0 1V 0 5V 0 10V 0 20mA 4 20...

Страница 10: ...A D n c n c 2 1 4 3 5 RS485 B D GND RS485 shielded RS485 A D n c Modbus RTU n c Fig 8 Plug option E4 for EE310 front connector view Model Supply Input Terminals Voltage Frequency EE310 with option E4...

Страница 11: ...J3 Modbus RTU 0 5V SELV Limited Energy source RS485 A D 2 RS485 B D 4 GND RS485 5 Tab 4 M12 connector Modbus RTU 3 2 4 Connection diagram Options E6 and E12 power supply analogue output 1 2 3 4 5 GND...

Страница 12: ...5 B D 4 GND RS485 5 Tab 6 M12 connector Modbus RTU 1 and or 2 3 2 5 Connection diagram Conduit option Conduit option electrical connection on terminal block in bottom housing part Conduit fitting opti...

Страница 13: ...rminals Voltage Frequency EE310 Indoor use 12 to 30Vac 50 60Hz Class 2 supply 8 35Vdc LPS Outdoor use 12 to 16Vac 50 60Hz Class 2 supply 8 35Vdc LPS V 1 GND 2 Outputs Model Type Ratings Terminals EE31...

Страница 14: ...c Power supply 100 240 V AC for polycarbonate enclosure 2 1 4 3 5 RS485 B D GND RS485 shielded RS485 A D n c Modbus RTU n c Fig 12 Plug option AM3 for EE310 front connector view External diameter of...

Страница 15: ...nalogue and digital output 3 2 7 Connection digram for integrated power supply module AM5 Wire size 30 16AWG Type CU Terminal torque USA 7 Lb In CANADA 0 8 Nm Fig 13 Option AM5 with liquid tight condu...

Страница 16: ...ND RS485 5 Tab 9 Electrical connection for integrated power supply module AM5 3 2 8 Connection diagram for alarm outputs AM2 For indoor use surface mounted according NFPA 79 applications only NO NC C...

Страница 17: ...A 0 7 Nm Model Supply Input Terminals Voltage Frequency EE310 with option AM2 12 to 30Vac 50 60Hz Class 2 supply 8 35Vdc LPS V 1 GND 2 Outputs Model Type Ratings Terminals EE310 with option AM2 Out 1...

Страница 18: ...ply Input Terminals Voltage Frequency EE310 with option AM6 Relay 1 Max switch load 250 Vac 6 A and 28 Vdc 6 A Min switch load 12 Vacdc 100 mA C 5 NO 4 C 5 NC 6 EE310 with option AM6 Relay 2 Max switc...

Страница 19: ...r surface mount transmitters For mounting template of enclosure see chapter 3 1 Mechanical installation Fig 4 Dimensions and mounting template of polycarbonate enclosure in mm inch T working range 40...

Страница 20: ...mounting flange see chapter 8 Replacement parts Accessories The immersion depth is adjustable The probe shall be horizontal In case of mounting into a separation wall it is of paramount importance for...

Страница 21: ...paramount importance to avoid T gradients along the probe In case of large T difference between the front and the back of the probe it is highly recommended to insert the probe completely into the pro...

Страница 22: ...ring probe installa tion may deviate by max 40 C 72 F from the regular temperature during normal operation Replace the metal sealing ring see Fig 19 Installation of the EE310 probe directly into the p...

Страница 23: ...force of the clamping sleeve This leads the risk of sudden expulsion of the sensing probe due to the pressure A torque higher than 30 Nm may lead to permanent deformation of the clamping sleeve and t...

Страница 24: ...l pipe threads Never rotate the screw connection body Instead hold the screw connection body securely and turn the union nut Avoid unnecessary disassembly of unused pipe screw connections Installation...

Страница 25: ...RELAY 2 RELAY 1 AM2 AM6 Fig 23 Alarm module option AM2 AM6 AM6 In accordance with NFPA 70 NEC and with CSA C22 1 CEC Part 1 A switch or circuit breaker must be included in the installation It must be...

Страница 26: ...itching point Switching point Hysteresis Standard Inverted Normal state Switch window Measurand Switching point low Switching point Hysteresis Switching point high Switching point Hysteresis Standard...

Страница 27: ...National regulations for installation must be observed AM5 In accordance with NFPA 70 NEC and with CSA C22 1 CEC Part 1 A switch or circuit breaker must be included in the installation It must be mark...

Страница 28: ...int temperature C 32 bit float 31107 452 Dew point temperature F 32 bit float 31131 46A Frost point Dew point temperature C 32 bit float 31133 46C Frost point Dew point temperature F 32 bit float 3111...

Страница 29: ...er the USB cable is connected the transmitter is initialised and the configuration is loaded The green status LED flashes and indicates proper operation of the electronics Blind cover USB cable Fig 29...

Страница 30: ...ith push buttons 5 3 Chart Data logger The TFT display with the integrated data logging function saves all measured and calculated values to the internal memory The data logger has a real time clock U...

Страница 31: ...ter content ppm Wet bulb temp K Dew point K Frost point K Volume concentr ppm Scale minimum Scale maximum 1 Home button 2 Configuration incl data logger menu 3 Time scale for the graph 5 min 3 months...

Страница 32: ...on relay configuration mode set points state adjustment 1 and 2 point humidity temperature adjustment reset to factory adjustment calibration status configuration of Modbus RTU data transmission Devic...

Страница 33: ...le with 0 1 V output Tab 10 Overview of error codes Error category 1 non critical error can be solved by the user The display blinks and the buzzer beeps every 10 seconds The red status LED lights con...

Страница 34: ...opriate filter type Contact E E representative for advice High humidity values red LED blinks Water in sensing head Investigate the cause for water condensation Contact E E representative for advice I...

Страница 35: ...er Depending on the level of accuracy required the humidity reference can be Humidity Calibrator e g Humor 20 please see www epluse com humor20 Handheld device e g Omniport30 please see www epluse com...

Страница 36: ...3 1 all versions Mating plug for integrated power supply AM3 Mating plug RKC 5 7 AM3 E4 E6 E12 Mating plug RSC 5 7 2 pcs for option E12 E5 E6 E12 Other languages can be downloaded at www epluse com EE...

Страница 37: ...ncluding 2 voltage or current outputs display and relay option AM2 or AM6 AM3 and AM5 option max 5 VA Including 2 voltage or current outputs and display option Pressure range for pressure tight probe...

Страница 38: ...asurands brightness display alarm output configuration mode measurands scaling error indication relay configuration mode set points state adjustment 1 and 2 point humidity temperature adjustment reset...

Страница 39: ...TU lb Frost point C Frost point F Water activity aw Saturation Water content ppm Wet bulb temp K Dew point K Frost point K Volume concentr ppm Layout Display settings Measurand 2 Measurand 1 Measurand...

Страница 40: ...C Wet bulb temp F Abs humidity g m Abs humidity gr ft Mixing ratio g kg Mixing ratio gr lb Enthalpy kJ kg Enthalpy ft lbf lb Enthalpy BTU lb Frost point C Frost point F Water activity aw Saturation Wa...

Страница 41: ...ing system Working pressure Probe replacement Parameters Humidity coefficient Resistance R0 Capacity C76 Capacity gain Capacity offset Temperature coefficient TK Resistance Offset Code Daylight saving...

Страница 42: ...steresis Standard Inverted Normal state Error indication Standard Inverted Normal state OFF Temperature C Temperature F Temperature K Rel humidity Vap p pressure mbar Vap p pressure psi Dew point C De...

Страница 43: ...Modbus RTU 8 E12 conduit fitting E23 liquid tight 1 2 conduit fitting E24 Optional features TFT colour display with integrated data logger 2 D2 Modbus RTU J3 E E sensor coating C1 alarm outputs 3 4 A...

Страница 44: ...w epluse cn BEIJING Tel 86 10 84992361 info epluse cn SHANGHAI Tel 86 21 61176129 info epluse cn E E GERMANY www epluse de Tel 49 6172 13881 0 info epluse de E E FRANCE www epluse fr Tel 33 4 7472 35...

Отзывы: