Operating instructions for EE310 Humidity / Temperature Transmitter
Model
Supply Input
Terminals
Voltage/Frequency
EE310 with option E4
Indoor use:
12 to 30Vac, 50/60Hz (Class 2 supply)
8-35Vdc (LPS)
Plug pin
V+ (1) –
GND (3)
Outputs
Model
Type
Ratings
Terminals
EE310 with option E4
Out 1
0-1V
0-5V
0-10V
0-20mA
4-20mA
(SELV Limited Energy source)
Plug pin
Out 1 (2) –
GND (5)
Out 2
0-1V
0-5V
0-10V
0-20mA
4-20mA
(SELV Limited Energy source)
Out 2 (4) –
GND (5)
Tab. 5
M12 connector power analogue output
Outputs
Model
Type
Ratings
Terminals
EE310 with option
E5 and J3
Modbus RTU
0-5V
(SELV Limited Energy source)
RS485 A (=D+) (2) –
RS485 B (=D-) (4) –
GND RS485 (5)
Tab. 6
M12 connector Modbus RTU 1 and / or 2
3.2.5 Connection diagram Conduit option
Conduit option (electrical connection on terminal block in bottom housing part)
Conduit fitting option E23
Liquid-tight conduit fitting option E24
Note for E23:
½” NPSL Flexible Nonmetallic Cord Connector is installed. Cable used for installation shall be suitable
flexible listed cord/cable in accordance with NEC. Clamping range grommet 6 to 10mm
(0.24 - 0.4”)
.
Local regulation for installation must be observed. Indoor use and dry location only. Not suitable for
mains voltage (110 - 240 Vac)
Note for E24:
½” Liquid-Tight Flexible Nonmetallic Conduit Type B (FNMC-B) is installed. Cable used for installation
shall be suitable flexible listed cord/cable in accordance with NEC.