DYNISCO UPR800 Series Instruction Manual
Page | 11
Engineering Units:
Dedicated beacons within the display window.
Calibration mode:
Field calibrations (zero and span) are applicable for both strain gage
and linear input. Moreover it is possible to delete the field calibration done by the end user
and to restore original factory calibration values.
Input resolution:
4000 counts.
Full scale value
Resolution
10/4000 1
count
4002/8000 2
counts
8005/20000 5
counts
20010/40000 10
counts
40020/80000 20
counts
80050/99950 50
counts
Decimal Point
Settable in any position of the display.
2.5 Secondary Input (optional)
Temperature Input:
Selectable between linear, thermocouple or RTD input by software
configuration.
Function:
Selectable between: temperature (in case of linear, thermocouple, RTD the
input); second sensor for the measurement of a differential pressure (in case of strain
gage or linear input)
Linear Input:
Selectable between 0-5Vdc, 0-10Vdc, 0-20mA, and 4-20mA