Pressure standby Recover Time Enter Value of time allowed for control output to be in saturation before turning
output off, from 0 to 60 secs
Pressure Standby active Limit
Enter Value of allowed control output power value that is applied once PV enters
Stable Band 0-100% Default: 20% Caution: Limits Max+ Min Output Power Value
Output Configuration:
Linear Output n Type
w From: 0-5, 0-10, 1-5, 2-10V & 0-20, 4-20mA or 0-10VDC adjustable Transmitter PSU.
Adjustable 0-10V Transmitter w Voltage required if Output n is 0-10VDC adjustable Transmitter PSU.
Output n Usage
w From: Alarms; Retransmit Process Variable .Primary Power, Secondary Power and
Unused.
Output n Alarm Selection w Alarm 1; 2; 3; or Logical OR of alarms 1 to 2; 1 to 3;. Selectable Direct or Reverse
Action.
Retransmit Output n Scale Low w Displayed value at which the retransmission output = minimum. Adjustable from
-1999 to 9999.
Retransmit Output n Scale High w Displayed value at which the retransmission output = maximum. Adjustable from
-1999 to 9999.
Alarm Configuration:
Alarm n Type
w From: Unused; High; Low; Rate Of Signal Change per minute; PV Signal Break; PV-SP
Deviation, Band, Control Loop, Percentage Memory Used, High and Low Power
Alarm n Input Selection
From: Universal Input 1 or 2
Alarm n Value
w Alarm activation point. – applicable if type is High; Low;Deviation;Band.
Alarm n Hysteresis
Deadband on “safe” side of alarm, through which the signal must pass before alarm
deactivates.
Signal change Alarm n Min.
Minimum time the rate of PV change must be above the alarm threshold for a Rate
Of Change Alarm to change state (on or off). 1 to 9999 secs.
Alarm n Inhibit
Prevents alarm activation if the alarm condition is true at power up. Activation
occurs only after the condition has passed and then reoccurred.
Alarm n Filter Time
Filter the time the alarm needs to be active for the action to take place from 0.5s to
100s
Control loop Alarm Type
Manual Loop alarm time, from 1s to 59minus 59s or Automatic (2× integral)
Percentage of Memory used
0-100%
High or Low power value
0-100%
Communications Configuration:
No Comms Warning
If Communications Configuration menu is entered without a communications
module fitted.
Modbus RTU Parity
w From: Odd; Even or None.
Modbus RTU Data Rate w From: 9600; 19200; 57600 or 115200 bps.
Master Mode, or Slave Address w Slave address (1 to 255), or multi-zone Setpoint Master Mode.
Master Mode Format
The data format required by the attached setpoint slaves. From: Integer; integer with
1 decimal place & float.
Serial Communications Write Enable
Enables/disables writing via RS485 or Ethernet (if fitted). When disabled, all
parameters are read only.
Recorder Configuration:
Refer to the Supplementary Product Manual for information about the additional screens when Data
Recorder is fitted.
No Recorder Warning
If the Recorder Configuration menu is entered on an instrument without this option.
Recording In Progress Warning
If recording in progress when Recorder Configuration entered. - Access to the Start/
Stop or Abort screens only until the recording is stopped.
PSU n
Duration