41
Jbus
MODbus
Description
Display
Attribute
Address
Address
Code
265
264
Input fail safe
(“I.F.S”)
R
Range:
0 = Down scale burn out (Lo)
1 = Up scale burn out (Hi)
269
268
External contact function
(“E.C.”)
R
Range:
0 = Enable external contact for manual alarm reset (nr)
1 = Enable external contact for stop on measuresampling (Ho)
270
269
Contact status
(“C.S.”)
R
Range:
0 = The selected external contact function is performed with contact
open (OP)
1 = The selected external contact function is performed with contact
close (CL)
271
270
Alarm 1 operative mode
(“A1”)
R
Range:
0 = Low alarm with manual reset (LL)
1 = Low alarm with automatic reset (LA)
2 = High alarm with manual reset (HL)
3 = High alarm with automatic reset (HA)
4 = No alarm 1 (OFF)
272
271
Alarm 1 action
(“A1”)
R
Range:
0 = Relay energized in alarm condition (dir = direct action)
1 = Relay energized in no alarm condition(rEV = reverse action)
273
272
Alarm 1 Masking Option
(“A1”)
R
Range:
0 = Masking Option Disabled
1 = Masking Option Enabled
47