Dynamatic CES Скачать руководство пользователя страница 18

18 

1.  CES controller power is applied 

2.  Enable is not present 

3.  No fault is present 

4.  Test mode parameter No. 60 is set to the ON 

condition from the keypad and display board 

5.  CES circuit breaker opened to remove power 

6.  Main motor and press control power is OFF 

7.  Jumper across CR2 contacts 15 and 16 on TB14 

8.  Jumper across TD contacts 26 and 27 on TB14 

9.  Jumper control power across contacts 300 and 302 

10. Incoming leads 320, 321 and 334 removed from 

TB10.  Tape ends 

11. Jumper 115 volts from 302 to 320 and 301 to 334 on 

TB10 

12. CES circuit breaker closed to reapply power 

13. Clutch test and/or brake test performed as required 

14. CES circuit breaker opened to remove power 

15. Remove  jumpers and replace leads that were 

changed in steps 7, 8, 9, 10 and 11 above 

16. CES circuit breaker closed to reapply power 

17.  Exit test mode by setting parameter No. 60 to the 

OFF condition from the keypad and display board 

 

An LED located on the keypad and display board 

indicates the test mode.  The test mode is only de-

energized by setting parameter No. 60 to OFF.  The test 

mode is stored in non-volatile memory. 

 

Clutch Test Mode  -  In the test mode, the clutch test 

mode can be entered by setting the clutch test mode 

parameter to ON (parameter No. 61, up arrow (↑)). 

 

The clutch will be engaged full ON with the DMR 

automatically doing the following: 

 

1.  Issuing a clutch ON command 

2.  Setting reference to 100% 

3.  Setting feedback to 0% 

4.  Releasing the DMR inhibit 

 

In the clutch test mode, the clutch is de-energized by 

doing the following: 

 

1.  Setting parameter No. 61 to OFF (down arrow (↓)) 

2.  Exiting the test mode or 

3.  Entering the brake test mode 

 

De-energizing the clutch test mode initiates the following 

sequence: 

 

1.  Reference and feedback are set to 0% 

2.  DMR inhibit is activated 

3.  The clutch ON command is dropped after 450 

milliseconds 

 

Brake Test Mode - In the test mode, the brake test mode 

can be entered by setting the brake test mode parameter 

to ON (parameter No. 62, up arrow (↑)). 

 

The brake will be engaged full ON with the DMR 

automatically doing the following: 

 

1.  Issuing a brake ON command 

2.  Setting reference to 0% 

3.  Setting feedback to 100% 

 

In the brake test mode, the brake is de-energized by 

doing the following: 

 

1.  Setting parameter No. 62 to OFF (down arrow (↓)). 

2.  Exiting the test mode or 

3.  Entering the clutch test mode 

 

De-energizing the brake test mode initiates the following: 

 

1. Reference and feedback are set to 0% 

 

Test Mode Faults - Receiving an enable in the test mode 

will result in an enable in the test mode fault.  Sensing 

press movement in the test mode will initiate a press 

movement in the test mode fault. 

 

VIII.  READY MODE 

The CES controller will be in the ready mode if the 

following conditions exist: 

 

1.  CES control power is applied 

2.  It is not in the run, test or fault modes 

 

The ready mode will be indicated by the "Ready" LED on 

the keypad and display board. 

 

IX. SPEED CONTROL REFERENCE CLAMP 

The CES controller has a maximum speed setting.  If the 

press control sends a speed reference value that is 

greater than this maximum speed to the CES controller, 

the CES controller will clamp the reference at the 

maximum speed.  The “Referenced Clamped" LED will 

light on the keypad and display board, indicating that the 

reference is clamped. 

 

PRESS CONTROL PARAMETERS 

The press control may have constraints on changing of 

speeds and press drive parameters while the press is 

running.  The CES controller will change parameters as 

directed by the press control. 

 

Press control parameters are sent by the press control in 

a packet of bits representing ASCII characters.  The first 

two ASCII characters will be AA.  The packet length is 

68 characters.  Space characters are used to complete 

the 68-character packet.  Upon receiving an EE 

command, the AA packet will be transmitted back to the 

press control by the DMR for comparison to ensure its 

accuracy.  The AA will be changed to EE when sent 

back. 

 

Fault data is sent by the CES controller upon request of 

the press control.  The two ASCII characters of the 

"Request to Send Fault Data" will be BB.  The packet 

length of the request will be two characters.  The DMR 

will send the fault data in a packet of bits representing 

ASCII characters.  The first two ASCII characters will be 

BB.  The remaining characters will be four-digit numbers, 

Содержание CES

Страница 1: ...E S Stamping Press Controller INSTRUCTION MANUAL Revised 2019 7900 Durand Avenue Bldg 3 Sturtevant WI USA 53177 Toll Free 800 548 2169 Phone 262 554 7977 Fax 262 554 7041 Email sales dynamatic com Web www dynamatic com ...

Страница 2: ...re working on the unit REFER TO OSHA RULES AND REGULATIONS PARAGRAPH 1910 219 FOR GUARDS ON MECHANICAL POWER TRANSMISSION APPARATUS NOTE Since improvements are continually being made to available equipment the enclosed data is subject to change without notice Any drawings are for reference only unless certified For additional information contact your nearest Eddy Current Representative listed in t...

Страница 3: ...rface Serial 13 Signals for Customer s Recorder 13 Analog Meters 13 Brake Contactor 13 Press Operating Modes 13 Press Control Parameters 18 SECTION 3 OPERATION Purpose 21 Constant Energy System 21 Stamping Press Operation 21 Eddy Current Clutch and Brake 21 Variable Speed Press Drives 21 Power Amplifier 22 CES Logic Board 23 Logic Power Supply Inputs 23 Logic Control Lines 23 LEM Current Feedback ...

Страница 4: ...r maintenance TRAINING Training programs are an essential part of safe and correct operation Training provides the knowledge necessary to obtain top performance from your equipment DSI Dynamatic recognizes this fact and conducts training schools to educate your plant personnel in safe maintenance and operating procedures Training schools are held at company headquarters in Sturtevant Wisconsin The...

Страница 5: ...tored equipment even if all procedures are followed damage or deterioration may still occur Equipment storage is not covered by warranty ELECTRICAL PART NUMBERING SYSTEM The numbering system for electrical component and assembly part numbers contains some useful data that could be of value to the technician working with or troubleshooting the controller The number is twelve digits arranged in a tw...

Страница 6: ...r in this family is a 54 000045 0102 The last four digits describe a specific part within the family and may be assigned in numerical sequence or may describe the specific part value The following table lists those part categories where the last four digits have a significant meaning to the technician Category Part Name Parameter Described 23 Capacitor Capacitance 32 Fuses Ampere rating 49 Potenti...

Страница 7: ...7 ...

Страница 8: ...transformer T1 Fuses FU5 and FU6 protect T1 against short circuits and internal grounds Capacitors C3 C4 and C5 along with the impedance of the autotransformer serve to filter the incoming power to prevent line noise from affecting the controller and to reduce line disturbances by the controller The autotransformer steps up the line voltage from 480 VAC to 600 VAC FU1 FU2 and FU3 are fast acting s...

Страница 9: ...TTING DIODE LED INDICATORS In addition to the LED noted for the keypad programmer LED indicator lights are also located on the printed circuit boards where operating circuit conditions need to be known The printed circuit boards that have LED s are described below LOGIC INTERFACE INDICATOR PCB 15 242 57 Refer to Figure 2 2 for the identification of the LEDs found on this printed circuit board CLUT...

Страница 10: ...s only called upon to function during periods where there is no power applied to the control Therefore the life of the battery may greatly exceed the ten year period if there are no extensive periods where the control is actually turned off Once the parameter values have been set the system may be run by activating the appropriate signals in the control circuitry High voltage input and output sign...

Страница 11: ...ain of events that provides for the integrity of the enable signal given by the press control to the CES controller Redundant CES inputs are provided to ensure that the enable signal is present and that the receiver is not shorted The enable signals consist of two press control contact closures that put the 115 VAC of the press control into the I O board CLUTCH CONTACTOR ON INPUT In addition to th...

Страница 12: ...nt solid state output signals that function as contact closures and contact openings according to the conditions called for The output signals that occur during different phases of operation are as follows Normal Stop Stop Main Motor Fault Stop Now Fault Stop on Top Fault Control Failure Fault Clutch ON and TD Relay NORMAL STOP OUTPUT The normal stop signal from the CES controller indicates that t...

Страница 13: ...rating parameters They are as follows 1 Clutch ammeter 2 Brake ammeter 3 Speed indication SPM 4 Elapsed time for clutch ON time BRAKE CONTACTOR A brake contactor is provided which will be closed under simultaneous conditions of control power ON being available and brake current fault not being present The brake contactor is opened 10 seconds after stopping on top when a brake current fault is pres...

Страница 14: ...a 5 manual Run Speed trim pot while still others function without any speed pot Both pots are effective when the press starts up and after the press passes Angles No 1 II INCH FORWARD MODE RUN AT The CES controller will be in the inch forward mode if the following conditions exist 1 Enable signal is present 2 No fault is present 3 Reverse is not present 4 Inch is present 5 Micro inch is not presen...

Страница 15: ... the enable signal The micro inch forward mode will be indicated by the Micro Inch LED on the keypad and display board V MICRO INCH REVERSE MODE RUN AT The CES controller will be in the micro inch reverse mode if the following conditions exist 1 Enable signal is present 2 No fault is present 3 Reverse is present 4 Inch is not present 5 Micro inch is present 6 Clutch contactor ON signal is present ...

Страница 16: ...n the clutch coil when CR1 is de energized a clutch current delay fault will be issued 0206 Press Movement in Wrong Direction Fault Press movement detected to be in a direction opposite of that commanded based upon degrees of opposite rotation after enabled The number of degrees of rotation before causing this fault is adjustable from 0 to 10 degrees at the keypad Set for minimum degrees without c...

Страница 17: ...from 3 to 20 seconds and the current allowable is 20 The CES controller cannot be enabled until cool down tine has expired 0317 Inch Change Fault If the inch command signal is changed while enable is present an inch change fault will exist 0318 Micro Inch Change Fault If the micro inch command is changed while enable is present a micro inch change fault will exist 0319 Reverse Change Fault If the ...

Страница 18: ...g the following 1 Issuing a brake ON command 2 Setting reference to 0 3 Setting feedback to 100 In the brake test mode the brake is de energized by doing the following 1 Setting parameter No 62 to OFF down arrow 2 Exiting the test mode or 3 Entering the clutch test mode De energizing the brake test mode initiates the following 1 Reference and feedback are set to 0 Test Mode Faults Receiving an ena...

Страница 19: ...er the CES controller has received the stop on top contact closure 4 The eighth angle will be the angle to initiate the contact that will allow the press control to set the friction brake after the press has been at creep speed and reaches this stop angle 5 The angles will be four digits with an implied decimal point in tenths of a degree ranging from 0 to 359 9 degrees 6 The speeds will be four d...

Страница 20: ...1 180 degrees 2 Manual Speed pot 16 SPM 3 Angle No 2 115 degrees 4 Speed No 2 10 SPM 5 Angle No 3 360 degrees 6 Speed No 3 10 7 Angle No 4 360 degrees 8 Speed No 4 10 9 Angle No 5 360 degrees 10 Speed No 5 10 11 Angle No 6 360 degrees 12 Speed No 6 10 13 Creep Angle 305 degrees 14 Stop Angle 356 5 degrees 15 On the keypad enter Creep Speed 3 SPM ...

Страница 21: ...r an eddy current clutch rotor and a brake rotor assembly directly connected to the press drive shaft Driving torque is developed through an electromagnetic force between the flywheel and clutch rotor Braking torque is developed through a similar force between the stationary brake field assembly and the brake rotor Electromagnetic coils in the flywheel or brake field assembly are energized to esta...

Страница 22: ... the opposite effect takes place The tachometer feedback voltage then exceeds the reference and the clutch error amplifier drives the clutch power amplifier off This puts a positive input on the brake error amplifier driving the brake power amplifier on By braking to slower speeds the tachometer feedback voltage is reduced in direct proportion to the reduction of the press speed until the speed re...

Страница 23: ...prevent overlap by producing a high on the control line Any high on the control line inhibits further operation A high on the control line can also be caused by other factors For the clutch it can be caused by the absence of a run signal input clutch contactor not pulled in DMR inhibit signal present 120 rated clutch coil current or 85 rated line voltage or missing phase For the brake it can be ca...

Страница 24: ...Speed of press SPM 36 Angle No 4 0 359 9 Degrees 37 Speed No 4 Speed of press SPM 38 Angle No 5 0 359 9 Degrees 39 Speed No 5 Speed of press SPM 40 Angle No 6 0 359 9 Degrees 41 Speed No 6 Speed of press SPM 42 Creep Angle Degrees 43 Stop Angle 5 Degrees 44 Creep Speed 5 SPM 45 Micro Inch Speed 25 of max SPM 46 Inch Speed 50 of max SPM 47 Inch Accel Rate 1 100 SPM Sec 48 Initial Value of Linear Ac...

Страница 25: ...ector Parameters are selected for viewing by first selecting either the top or bottom display window called the active display and then entering the 2 digit code for that parameter in the parameter number field The top display windows are selected by pressing the Top button on the keypad and similarly the bottom display windows are selected by pressing the Bot key When the display windows become a...

Страница 26: ...ow button for a period longer than one second the up down function will revert back to normal speed of operation A faster up down function is also available By first pressing the key and then either the Up or Down arrow button the increment of change will be by 100 units per increment Any attempt to change a non alterable display parameter will be ignored ...

Страница 27: ...s will Stop On Top In other words if the signal is present when the set Creep Angle is reached the press will continue at Run Speed into the next stroke This is the equivalent of the continuous mode of operation If the signal is not present at this point the press will go to Creep Speed If after being programmed to Creep Speed the signal is present when the press reaches the set Stop Angle the pre...

Страница 28: ...ng 450 ms Time Delay 27 Max AC Line Voltage 0226 Clutch Contactor On w o Enable 28 Max Cl Cur Scaling Factor Amps 0227 Enable Before Cool Down Expired 29 Max Br Cur Scaling Factor Amps 0228 Creep Sp Not Reached Before Stop Angle 30 Angle 1 DEG 0313 Under speed 31 Speed 1 SPM 0314 Clutch and Brake Current Overlap 32 Angle 2 DEG 0315 Clutch Current 33 Speed 2 SPM 0316 Brake Current 34 Angle 3 DEG 03...

Страница 29: ...oltage 0224 Stop On Top Not Performed 28 Max Cl Cur Scaling Factor Amps 0225 Cl Contactor On Removed w o Removing 29 Max Br Cur Scaling Factor Amps Enable or During 450 ms Time Delay 30 Angle 1 DEG 0226 Clutch Contactor On w o Enable 31 Speed 1 SPM 0227 Enable Before Cool Down Expired 32 Angle 2 DEG 0228 Creep Sp Not Reached Before Stop Angle 33 Speed 2 SPM 0313 Under speed 34 Angle 3 DEG 0314 Clu...

Страница 30: ... used to fire the SCRs that provide the power required to maintain the set speed 2 Limits the clutch current to a value equal to the rating of the mechanical unit 3 Limits the brake current to a value equal to the rating of the mechanical unit 4 Provides adjustable velocity damping to the clutch circuitry 5 Provides adjustable velocity damping to the brake circuitry 6 Provides clutch free wheel co...

Страница 31: ...ON position h The DMR will remember that it is in the test mode 60 On will reappear in the top row of display i The test mode will be indicated by the Test LED on the keypad and display board 5 Enter the clutch test mode a While in the test mode the clutch test mode can be entered by setting the clutch test mode parameter No 61 to ON Proceed as follows 1 Press the Bot key This will activate the bo...

Страница 32: ... fault will be generated Check this LED on the I O board Since the press is not rotating it will not get to the creep angle or the stop angle therefore a stop now fault will be generated Check this LED on the 1 0 board 6 Send the clutch contactor ON signal without the enable signal A stop now fault will be generated 7 Send the enable signal without the clutch contactor ON signal A stop now fault w...

Страница 33: ... the Inch pushbutton for this jog function 14 Check the Remaining Faults APPROXIMATE PARAMETER SETTINGS Approximate parameter settings which are furnished for trial only are indicated in Table 4 1 Actual settings will be determined during the press set up If for security reasons the customer removes the ribbon cable connecting the keypad to the DMR care must be exercised in removing the power to t...

Страница 34: ...0 0 52 100 0 58 5 0 54 5 0 55 100 0 56 100 0 57 100 0 58 5 5 59 5 5 60 Off 61 Off 62 Off 63 Clear 64 10 0 65 10 0 66 300 0 67 2 0 68 2 0 69 10 0 70 3 0 71 1 72 1 0 73 9600 0 74 10 0 75 120 0 76 See resolver adjustments under Start Up Section 77 See resolver adjustments under Start Up Section 78 See press specifications 79 See speed reference section 80 Self Explanatory 81 150 0 82 170 0 83 3 0 NOT...

Страница 35: ...ds at the controller terminal strip and check the resistance of the coil and resistance to ground Check the drive nameplate or contact the Field Service Department at the factory for the coil resistance Resistance to ground should be about 20 megohms When using a megger make sure both coil leads are disconnected from the controller Do not megger any portion of the controller If the drive is errati...

Страница 36: ...eplacement Technical assistance is available over the telephone and field service engineers are available for start up troubleshooting and training You may inquire about rates and scheduling from the factory The company maintains a Repair Service Department and work is done on a time and material basis All replacement boards will carry a new factory warranty Refer to Tables 2 1 and 2 2 for DMR ass...

Страница 37: ...Page is intentionally blank ...

Страница 38: ...DRIVE SOURCE INTERNATIONAL INC 7900 Durand Avenue Bldg 3 Sturtevant WI USA 53177 Toll Free 800 548 2169 Phone 262 554 7977 Fax 262 554 7041 Email sales dynamatic Web www dynamatic com ...

Отзывы: