Status
Switch position
Description
Ready for operation (=
ready)
The voltage supply is functioning,
the boot process of the device has
completed, and there are no faults
in the system. The relay has been
activated.
Not ready
The voltage supply is off/interrupted
or the boot process of the device
has not yet completed, or there is a
fault in the system. The relay has
dropped/is without power.
Table 6.6: READY contact
The changeover contact position for the status “ready” is displayed on the device. The IRIS-
Net software allows the user to configure the fault types for which the changeover contact
should switch over and signal the status “Not ready”. To integrate the DPM 8016 into the
hazard alert systems, a normally-closed contact (standby current principle) is recommended,
i.e., the left and middle pin.
!
Caution!
The maximum load of the ready contact is 30 V/1 amp.
Radio clock input (DCF77)
The top half of the control port has an input for the radio receiver of the DCF77 signal. We
recommend using the DYNACORD NRS 90193 receiver. Observe the delivered documentation
when connecting the receiver to the DPM 8016.
Slave clock output (SC OUT)
The lower half of the control port has a special, short-circuit-proof output for polarity switch
impulses. Slave clocks connected here are automatically adjusted if a time difference is
detected between the slave clocks and the system clock, for example after a power failure or
in the event of manual input. Ensure that all slave clocks are connected with the same polarity.
Notice!
The maximum permissible number of slave clocks on the SC OUT output depends on the
power consumption of the slave clock type used. Example: When using a slave clocks type
with a power consumption of 12 mA up to 80 slave clocks can be connected.
24
en | Connections
DPM 8016
16-Dec-13 | 02 | F01U259190
Operation manual