Figure 6.8: Sample application of a control input and use of 2 digital inputs signals
Control outputs (CONTROL OUTPUTS)
The lower half of the control port has six freely programmable control outputs numbered 1
through 6. In inactive mode (Off), these control outputs are open, while in active mode (On),
they are closed to ground. To operate the externally connected elements, a voltage source is
available on the connection 24/48V/200mA; see also the following diagram.
Notice!
The voltage value used as the supply voltage for the DPM 8016 controller is always present on
the 24/48V output.
!
Caution!
The maximum permissible power on the 24/48V output is 200 mA.
Figure 6.9: Sample application of a control output
Ready contact (READY)
The lower half has a potential-free READY changeover contact. This changeover contact signals
to other devices that the DPM 8016 is ready for operation or indicates faults in the system.
The following table shows the possible statuses of the ready contact.
DPM 8016
Connections | en
23
Operation manual
16-Dec-13 | 02 | F01U259190