Page 28
If
Out1
is set for
##tP, #PUL,
or
ProP
, then
S1OL
and
S1OH
(following) appear. If
Out1
is set for
ONOF
, then skip to
S1rE
.
S1OL
Set Point Output Low Limit: Select
0
to
100
% but not greater than
S1OH
. This item limits the
lowest output value. This is useful for adding a bias to the process when needed. Factory
set to
0
for output codes 1,2, and 3. Factory set to
20
for output code 5 (20% output equals
4 mA output).
S1OH
Set Point 1 Output High Limit: Select
0
to
100
% but not less than
S1OL
for output codes 1,
2, or 3. Select
0
to
102
% but not less than
S1OL
for output code 5. This item allows setting
the maximum output limit. This is useful with processes that are overpowered. Adjustment to
102% allows setting current output to force a full on condition for output devices which do
not have bias adjustments. Factory set to
100
for all output codes.
If
Out1
is set for
##tP, #PUL
, or
ProP
, then skip to
S1LP
on next page.
S1rE
Set Point 1 Reset. Select
OnOF
or
Hold
.
OnOF
Control will automatically reset when process passes back through
SP1d
.
HoLd
Manual Reset. Reset (acknowledge) by simultaneously pressing the
INDEX &
DOWN ARROW
keys for 5 seconds.
S1Pi
Set Point 1 Power Interrupt. Select
On
or
OFF
.
On
Alarm Power Interrupt is
On
. Control will automatically reset on power-up if no
alarm condition exists.
OFF
Alarm Power Interrupt is
OFF
. Control will power-up in alarm condition regardless
of condition of process.
S1iH
Set Point 1 Inhibit: Select
On
or
OFF
.
On
Alarm Inhibit is
On
. Alarm action is suspended until the process value first enters
a non-alarm condition.
OFF
Alarm Inhibit is
OFF
.
S1LP
Set Point Lamp: Select
O on
or
OoFF
.
O on
Lamp ON when Output is ON.
OoFF
Lamp OFF when Output is ON.