Page 20
SECONDARY MENU
Hold
UP ARROW & ENTER
. Press
INDEX
to advance to the next menu item. Press
UP ARROW
or
DOWN ARROW
to change the value in the display. Press
ENTER
to retain the value.
If the control is not equipped with alarm, or if the alarm functions (
AL
) are turned
OFF
or programmed
as event (
Eunt
),
ALLO
and
ALHi
will not appear.
ALLo
Alarm Low: The Low Alarm point is usually set below the Set Point. May not appear depend-
ing on
AL
setting in
Secure Menu
.
ALHi
Alarm High: The High Alarm Point is usually set above the Set Point. May not appear
depending on
AL
setting in
Secure Menu
.
Out1
Output selection: Select
OnOf, 1tP, 1PuL,
or
ProP
.
ONOF
A setting of
ONOF
allows the control to operate as a simple on/off mode. This
setting forces the control to turn off at set point, and on at the set point plus the
differential (
SP_d
). When selected, the
Out1/OnOF
menu item is followed by
####/SP1d
, and the
tunE, Pb, rES, OFS, rtE,
and
ArUP
selections in the
Secondary menu and the
S1OL
and
S1OH
selections in the Secure menu are
suppressed.
SP_d
Set Point On-Off Differential (hysteresis). Select
1
to
9999
(direct acting), or
-1
to
-9999
(reverse acting). This value will be negative for reverse acting set
points, and positive for direct acting outputs. Set the value for the amount of
difference between the turn off point (set point) and the turn on point. The
following drawing shows output behavior for reverse and direct action.