FrtE
Fuzzy Logic Rate of Change: Select
0.00
to
99.99
counts/second. For best initial setting,
find the count/second change of process value near set point 1 with output ON 100%.
Multiply this value by 3. Set
FrtE
to this calculated value. Will not appear if
Fint
is
OFF
.
PEA
The Peak feature stores the highest input the control has measured since the last reset or
Power On. At Power On PEA is reset to the present input. To manually reset the value
PEA
must be in the lower display. Press the
ENTER
key to reset.
PEA
will be reset and display
the present input value.
UAL
The Valley feature stores the lowest input the Instrument has measured since the last reset
or Power On. At Power On
UAL
is reset to the present input. To manually reset the value
UAL
must be in the lower display. Press the
ENTER
key.
UAL
will be reset and display the
present input value.
PctO
Percent Output Feature: Select
On
or
OFF
.
On
When selected
On
, the HOME lower display will indicate the output of the
controller in percent. An “
o
” will appear in the right hand side of the lower display
to indicate percent output for SP1. An "
õ
" will appear on the right hand corner of
the lower display to represent percent output for SP2, if the control is so
equipped. The display will alternate between these values.
OFF
Percent Output display is disabled.
Prog
Ramp/Soak Feature: Select
On
or
OFF
On
Allows Programmed Ramp/Soak function to be started by the
Run/Hold key on the control front panel.
OFF
Turns Ramp/Soak function
OFF
and resets program to beginning.
PSEt
Programmer function set. Select
On
or
OFF
.
OFF
Skip Ramp/Soak Programming. Go to next Secondary Menu Item, In PC on the
next page.
On
Enable Ramp/Soak Programming.
StAt
Programmer Status Display in the Primary Menu when Prog (above) is On:
Select
On
or
OFF
.
OFF
The Primary Menu operates as normal.
On
The Primary Menu is altered to have the following items inserted before the SP1
menu item:
####/ti
(time remaining in segment),
####/##ti
(total time in active
segment), and
####/##SP
(segment target set point).
tbAS
Ramp/Soak Time Base. Select
1_S
or
60_S
.
1_S
Ramp/Soak time base is in 1 second increments. Program time
1ti...16ti is measured in seconds.
60_S
Ramp/Soak time base is in 60 second increments (minutes).
Program time 1ti...16ti is measured in minutes.