37
Damping
• This value determines the amount of time the velocity is averaged. The
display value will reach 99% of the measured value within this time.
• Default: 30 s.
Calibration Factor
• This value sets a custom multiplier of the measured velocity.
• Default: 1.000.
Save Defaults
• This menu saves the current configuration as the user default values. This
provides a means to save a known good configuration before making other
changes.
• Default: Yes.
Restore Defaults
• This menu restores the saved user configuration to the current configuration.
This provides a means to restore the meter to a known working state.
• Default: No.
Indicator Display Setup
• If a remote indicator display is being used, select which values should be
displayed.
• Default: V. Flow & Velocity
Reset to Factory Default
This special menu is accessed by press & holding ENTER
and MENU
buttons on the Device Information screen above. Answering Yes will reset all
selections and values to factory default values.
Key Pad Lockout Feature
• In units with the LCD option, a switch (shown in Figure 25) is located on
the display board that locks out the keypad to prevent undesired key presses
that could potentially change the meter configuration. When the switch is in the
“locked” position, the display will generate a padlock symbol in the lower right
corner as shown below.
• Default: Unlocked.
Figure 25: Keypad lockout switch
KEYPAD LOCKOUT SWITCH
All BACnet Communications settings will be reset as well, including
the values that can only be set via BACnet Communications.
NOTICE