25
Register
Description
Data Type
Range
0001-0002
0003-0004
0005-0006
0007-0008
0009
0010
0011-0012
0013-0014
0015-0016
0017-0018
0019-0020
0021-0022
0023-0024
0025-0026
0027-0028
0029-0030
0031
0032
0033
0034-0035
0036
0037
0038
0039-0040
0041
0042
0043
0044-0045
0046
0047
0048
0049-0050
0051-0052
0053-0054
8001-8016
8017-8020
8021-8028
8029-8032
8033-8036
8037-8044
8045-8048
Velocity
Volume Flow
Mass Flow
Total Flow
Reverse Flow
Empty Pipe
Flow Meter Status
Power
Total Energy
Inlet Temperature
Outlet Temperature
Temperature Difference
Heat Energy
Cooling Energy
Energy Totalized Hour Counter
YTD Max Power
YTD Max Power Date: Year
YTD Max Power Date: Month
YTD Max Power Date: Day
YTD Min Power
YTD Min Power Date: Year
YTD Min Power Date: Month
YTD Min Power Date: Day
MTD Max Power
MTD Max Power Date: Year
MTD Max Power Date: Month
MTD Max Power Date: Day
MTD Min Power
MTD Min Power Date: Year
MTD Min Power Date: Month
MTD Min Power Date: Day
Inlet YTD Average Temperature
Outlet YTD Average Temperature
Energy Meter Status
Model Number
Flow Meter Serial Number
Flow Meter Firmware Version
Flow Meter Date Code
Energy Meter Serial Number
Energy Meter Firmware Version
Energy Meter Date Code
32bit Float
32bit Float
32bit Float
32bit Float
Unsigned 16bit Integer
Unsigned 16bit Integer
Unsigned 32bit Integer
32bit Float
32bit Float
32bit Float
32bit Float
32bit Float
32bit Float
32bit Float
Unsigned 32bit Integer
32bit Float
Unsigned 16bit Integer
Unsigned 16bit Integer
Unsigned 16bit Integer
32bit Float
Unsigned 16bit Integer
Unsigned 16bit Integer
Unsigned 16bit Integer
32bit Float
Unsigned 16bit Integer
Unsigned 16bit Integer
Unsigned 16bit Integer
32bit Float
Unsigned 16bit Integer
Unsigned 16bit Integer
Unsigned 16bit Integer
32bit Float
32bit Float
Unsigned 32bit Integer
String
String
String
String
String
String
String
See BACnet “Flow Meter Status Flags”
See BACnet “Energy Meter Status Flags”
Example:
“IEF-HN-10-COM” or “IEFB-HN-PG-R10-COM”
“xxxxxxxx”
“x.x.x”
“xxxx”
“xxxxxxxx”
“x.x.x”
“xxxx”
The String data type is read as a
stream of ASCII characters with the first
character sent in the MSB of the first
register and the second character sent
in the LSB of the first register and so on.
If the string is shorter than the allotted
size, the remaining bytes will be zero
padded.
MODBUS
®
Modbus
®
Functions
The device supports the following functions
Modbus
®
Registers
Input Registers
Function Name
Function Code
Read Holding Registers
Read Input Registers
Write Single Register
Write Multiple Registers
03
04
06
16
Содержание IEFB Series
Страница 8: ...8 Figure 19 PCBA Figure 20 Wiring diagram...