18
Analog Value – Heat Energy
COV Increment Value
Supported Units:
Kilojoule (17), Megajoule (126), Gigajoule (522)*, Btus (20), Kilo-btus (147), Watt-
hours (18), Kilowatt-hours (19), Megawatt-hours (146), Ton-hours (22)
*Non-Standard BACnet unit
Analog Value – Cooling Energy
COV Increment Value
Supported Units:
Kilojoule (17), Megajoule (126), Gigajoule (522)*, Btus (20), Kilo-btus (147), Watt-
hours (18), Kilowatt-hours (19), Megawatt-hours (146), Ton-hours (22)
*Non-Standard BACnet unit
Analog Value – Cooling Energy
COV Increment Value
Supported Units:
Degrees-Celsius (62), Degrees-Kelvin (63), Degrees-Fahrenheit (64), Degrees-
Rankine (523)*
*Non-Standard BACnet unit
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out of Service
Units
COV Increment
Property List
AV6
"Heat Energy"
ANALOG_VALUE (2)
Current reading
0
Normal (0)
NO_FAULT_DETECTED (0)
FALSE (0)
Kilojoule (17)
1.0
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetEngineeringUnits
Real
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out of Service
Units
COV Increment
Property List
AV7
"Cooling Energy"
ANALOG_VALUE (2)
Current reading
0
Normal (0)
NO_FAULT_DETECTED (0)
FALSE (0)
Kilojoule (17)
1.0
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetEngineeringUnits
Real
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out of Service
Units
COV Increment
Property List
AV7
"Cooling Energy"
ANALOG_VALUE (2)
Current reading
0
Normal (0)
NO_FAULT_DETECTED (0)
FALSE (0)
Kilojoule (17)
1.0
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetEngineeringUnits
Real
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read
Default Value Minimum Value Minimum Value Increment
1.0 kJ
1.0 kJ
10000 kJ
1.0 kJ
Default Value Minimum Value Minimum Value Increment
1.0 kJ
1.0 kJ
10000 kJ
1.0 kJ
Default Value Minimum Value Minimum Value Increment
1.0°C
0.1°C
10.0°C
0.1°C
Содержание IEFB Series