34
Communication Configuration Wizard
1. If Continue is selected, the next menu displayed will be the Communication
configuration wizard.
2. If Save & Exit is selected, the settings and values entered during the Alarm
configuration wizard will be stored and put into effect.
3. Regardless of the selection, the ENTER
button must be pressed to show
process data.
• Default: Continue.
4. Select Protocol Menu:
• This option determines the protocol used by the meter over the RS-485
interface.
• Default: Disabled.
5. Network Address Menu:
• This value sets the device address on the RS-485 bus. Address range
depends on protocol; BACnet Communications Protocol (0-127), Modbus
®
Communications Protocol (1-247)
• Default: 127
6. Baud Rate Menu:
• This option selects the communication speed of the RS-485 bus.
• Default: 19200 (Modbus
®
Communications Protocol), 38400 (BACnet
Communications Protocol)
7. Serial Parity Menu (Modbus
®
Communications Protocol Only):
• This option sets the serial parity on the RS-485 bus.
• Default: Even.
8. Serial Stopbits (Modus
®
Communications Protocol Only):
• The option sets the serial Stopbits on the RS-485 bus.
• Default: 1.
9. Communication Summary Display:
• This screen shows a summary of the settings entered in the Communication
configuration wizard.
• After the Communication Wizard is complete, the meter setup is complete.
• The display will show Setup Complete and transition to display process
Data.