13
Network Termination Jumper
On the terminal block PCBA there is a jumper, J1 (see Figure 24), that enables or
disables a network termination resistor as defined below:
When the network jumper is in the ON position there is a 120 ohm termination resistor
in place. When the network jumper is in the OFF position there is no termination
resistor in place.
Default: OFF
IEFB: Communication Overview
The IEFB supports BACnet MS/TP and Modbus
®
RTU over 2-wire RS485. Selection of
protocol and configuration of serial parameters require the use of the display.
NETWORK TERMINATION JUMPER
Figure 24: Network termination jumper
Object Type
Dynamically
Creatable
Dynamically
Deletable
Object
Identifier Object Name
Device
No
No
607XXX “Series IEF 607xxx” or
“Series IEFB 607xxx”
Analog Input
No
No
AI1
AI2
AI3
Velocity
Inlet Temperature
Outlet Temperature
Analog Value
No
No
AV1
AV2
AV3
AV4
AV5
AV6
AV7
AV8
AV9
AV10
AV11
AV12
AV13
AV14
AV15
AV16
AV17
Volume Flow
Mass Flow
Total Flow
Power
Total Energy
Heat Energy
Cooling Energy
Differential Temperature
YTD Max Power
YTD Min Power
MTD Max Power
MTD Min Power
Inlet YTD Average
Temperature
Outlet YTD Average
Temperature
Heat Changeover
Temperature
Process Pressure
Ethylene Glycol
Concentration
Binary Value
No
No
BV1
BV2
BV3
BV4
Reverse Flow
Empty Pipe
Reset Total Flow
Reset Energy Statistics
Bit String
Value
No
No
BSV1
BSV2
Flow Meter Status Flags
Energy Meter Status Flags
Date Value
No
No
DV1
DV2
DV3
DV4
YTD Max Power Date
YTD Min Power Date
MTD Max Power Date
MTD Min Power Date
Multi-State
Value
No
No
MSV1
MSV2
Velocity Probe Location
RTD Locations
Positive
Integer Value
No
No
PIV1
Energy Hour Counter
BACNET
BACnet Object Overview
Supported BACnet Objects