Binary Value – Reset Energy Statistics
Writing a value of 1 to the present value of this object will reset all the energy statistics
to default values. Writing a value of 0 has no effect.
Objects affected: Total Energy (AV5), Heat Energy (AV6), Cooling Energy (AV7), YTD
Max Power (AV9), YTD Min Power (AV10), MTD Max Power (AV11), MTD Min Power
(AV12), Inlet YTD Average Temperature (AV13), Outlet YTD Average Temperature
(AV14), YTD Max Power Date (DV1), YTD Min Power (DV2), MTD Max Power (DV3),
MTD Min Power (DV4), Energy Hour Counter (PIV1)
Bit-String Value – Flow Meter Status Flags
Bit-String Value – Energy Meter Status Flags
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out Of Service
Property List
BSV1
“Flow Meter Status Flags”
BITSTRING_VALUE (39)
{}
0
NORMAL (0)
NO_FAULT_DETECTED(0)
FALSE (0)
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BitString
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out Of Service
Property List
BSV2
“Energy Meter Status Flags”
BITSTRING_VALUE (39)
{}
0
NORMAL (0)
NO_FAULT_DETECTED(0)
FALSE (0)
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BitString
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out Of Service
Property List
BV4
“Reset Energy Statistics”
BITSTRING_VALUE (39)
Inactive (0)
0
NORMAL (0)
NO_FAULT_DETECTED(0)
FALSE (0)
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BACnetBinaryPV
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Bit
Meaning when Set (1)
0
1
2
3
4
5
6
7
8
9
10
11
12
Error: Problem reading/writing NV storage
Error: Problem communicating with BTU module
Error: Problem communication with ADC
Error: Device recovered from Watchdog reset
Error: Factory settings invalid (using defaults)
Error: Wiring Board not installed/detected
Error: Flyback/Output board not installed/detected
Error: BTU board not installed/detected
Error: AFE board not installed/detected
Error: Coil Driver board not installed/detected
Error: Measured value is invalid
Error: Process Temperature Probe Missing/Broken
Error: Some Test Mode Active
Bit
Meaning when Set (1)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Error: Problem reading/writing NV storage
Error: Problem communicating with RTC
Error: Problem communication with ADC
Error: Device recovered from Watchdog reset
Error: Device recovered from External Reset
Error: Factory settings invalid (using defaults)
Error: Inlet temperature invalid
Error: Inlet Probe open circuit
Error: Inlet Probe short circuit
Error: Outlet temperature invalid
Error: Outlet Probe open circuit
Error: Outlet Probe short circuit
Error: Measured value is invalid
Error: Temperature delta is outside the required window
Error: Test Mode Active
Error: Calibration Mode Active