Alarm displayed
Potential cause
Action
CTO-CTO ELV
n
(
n= 1÷8
)
Short circuit of SOV No.
n
Check SOVs, coils and connections
MICRO 2 ALARM
ITVC failure
Reset alarm. If alarm persists, replace ITVC
MEMORY COMPARISON
ITVC failure
Reset alarm. If alarm persists, replace ITVC
MRT EXPIRED
Maximum Repair Time expired
Solve emergency and restore ITVC
CLOCK ERROR
ITVC failure
Reset alarm. If alarm persists, replace ITVC
R175
ITVC failure. Shunt 24Velv failure
Reset alarm. If alarm persists, replace ITVC
F20
ITVC failure. Fuse F20 Vreg interrupted. Probable
damage to SOV’s
Check SOV/s
Reset alarm. If alarm persists, replace ITVC
PERFORMING ESD
Electric ESD in progress
Solve emergency and restore ITVC
SAFETY ACTION
Safety action in progress
Solve emergency and restore ITVC
Battery
(only if
optional
battery is
present)
LOW BATTERY
Low battery voltage
Check power supply. Restore power supply
and after 2 hours check again alarm. If
necessary, replace battery
NO BATTERY
Low battery voltage or battery disconnected
Check if battery is activated in
Administrator menu. Check power supply.
Restore power supply and after 2 hours
check again alarm. If necessary, check
battery connections and/or replace battery
WARNING TABLE
Warning displayed
Potential cause
Action
SERVICE REQUEST
Set service time expired
Perform service/maintenance
HIGH TEMPERATURE
Max temperature set value exceeded
(75 °C)
Solve emergency and restore ITVC
ONLY ESD 1 ACTIVE
ESD1 and ESD2 signals different
Check wiring and ITVC ESD2 channel
ONLY ESD 2 ACTIVE
ESD1 and ESD2 signals different
Check wiring and ITVC ESD1 channel
MRT ALARM TABLE
MRT displayed
Potential cause
Action
CRC FLASH ERR
ITVC failure
Reset alarm. If alarm persists, replace ITVC
SENS
n
OUT OF RANGE (
n= 1÷3
)
Sensor No.
n
reading is out of range
Check sensor
n
. If necessary, replace it.
SENS
n
OUT COMP (
n= 1÷3
)
Sensor No.
n
reading is out of comparison and voting
process
Check sensor
n
. If necessary, replace it.
FAUTL OPTO ESD1
ITVC failure
Reset alarm. If alarm persists, replace ITVC
FAULT OPTO ESD2
ITVC failure
Reset alarm. If alarm persists, replace ITVC
FLASH ERROR
ITVC failure
Reset alarm. If alarm persists, replace ITVC
RAM ERROR
ITVC failure
Reset alarm. If alarm persists, replace ITVC
SW ERROR
ITVC failure
Reset alarm. If alarm persists, replace ITVC
WATCHDOG
ITVC failure
Reset alarm. If alarm persists, replace ITVC
SOV
n
FAULT (
n= 1÷8
)
Fault on SOV No.
n
Check SOV No.
n
. If necessary, replace it.
CLOCK ERROR
ITVC failure
Reset alarm. If alarm persists, replace ITVC
RAM CRC ERR
ITVC failure
Reset alarm. If alarm persists, replace ITVC
MRT MICRO 2
ITVC failure
Reset alarm. If alarm persists, replace ITVC