The actuator works according to the configured
actuator control mode, LOCAL, REMOTE, OFF
:
in
LOCAL
and in
HOME
page, the pushbuttons
are available for menu operations
In
LOCAL
and in
Local Command
page, the pushbuttons work as local Open/Close/Stop actuator
commands.
in
REMOTE,
the actuator is remotely controlled.
In
OFF,
any local or remote command to move the actuator is inhibited.
In
REMOTE
and
OFF
, the pushbuttons
and
are available for menu operations.
On request
OFF
can be disabled, in this case only LOCAL and REMOTE are available.
On request the pushbutton can be configured to work as “Local STOP active even if actuator control mode is
REMOTE”.
The procedures and figures in the next paragraphs use the
HOME
page “
standard type”
. In case of ITVC with HPU or
HIPPS control, the HOME page should be replaced by the HOME page “
HPU type
” and “
HIPPS type
”.
10.2 Actuator control mode
The following figure show the procedure to change the actuator control mode from
REMOTE
to
LOCA
L and to enter
in the
Local Command
page to move in open and close the actuator by the pushbutttons
and (see
configuration options in the paragraph “Local and Remote controls”, Administrator, SETUP menu). Password
Administrator is required. The current actuator control mode is visible in the HOME page, REM=REMOTE,
LOC=LOCAL, OFF=OFF.
Exit from
Local Command
page and return in
HOME
page is:
automatic
= no operation of pushbuttons is done in 2
min or
manual
= by pressing more than 3 sec, until the HOME page appears.
The same procedure can be used to switch from
LOCAL
or
OFF
to
REMOTE
. When the
Local Command
page
appears, press more than 3 sec, until the HOME page is available.
If the procedure is used to switch from LOCAL or REMOTE to
OFF
, the
Local Command
page is not present and the
display switches to HOME page from “Password confirmation” page.