9.7 Operating principle
9.7.1 Actuator control
The ITVC collects the
commands
from control room and HMI, the
feedback sensors
signals from H/PCU, Actuator
and Pipeline and
drives the Solenoid Operated Valves
of the
H/PCU
(Hydraulic or Pneumatic Control Unit)
to open
and close the process valve
by means of the single or double acting
actuator
. Three actuator control mode are
available:
LOCAL
,
REMOTE
and
OFF
. On request the
OFF
option can be removed.
In
LOCAL
, the actuator can be controlled by the local pushbuttons
, and
of HMI. If the display is in the
Local Command page
, they work as
open
,
close
and
stop
actuator commands (see par. Actuator Control mode).
In
REMOTE
, the actuator is remotely controlled by the OPEN and CLOSE digital inputs. Further digital inputs (ESD,
PST, etc.) are available to carry out special actions (safety valve positioning, command inhibit, etc.).
In
OFF
no command to move the actuator is available.
Both in
REMOTE
and
OFF
the local pushbuttons , , and are available to navigate in the HMI menu. In
LOCAL
they are available to menu operation only in HOME page. (see par. Actuator Control mode)
The
Control Logic
block handles the different source of inputs, drives the outputs, monitors the operation of the
complete system “ITVC-H/PCU-Actuator” and in case of malfunction generates
Alarms
,
MRT Alarms
, and
Warnings
and carries out the configured actions. The condition of Alarm/MRT Alarm is remotely signalled by the
Monitor Relay. Four additional relay are available to signal configurable status (end of travel, warnings, etc.). ITVC
status is also locally signalled by the HMI. The minimum duration of each Local and Remote controls is
300ms
In case of “
single acting spring return”
actuator, when the actuator reaches the electrical end of travel (by limit switch
or analogue position transmitter), the coil of the Solenoid Operated Valve controlling the process valve is kept
energized (or de-energized). In case of “
double acting
” actuator, when the actuator reaches the electrical end of travel
(by limit switch or analogue position transmitter), the coil of the Solenoid Operated Valve controlling the valve is kept
energized 5 sec and then it is released.
By the
ADMINISTRATOR
menu, in the
SETUP
chapter, the following control options can be set:
Local control mode:
o
Push to run
: the open and close commands is active for as long as the pushbutton
or is
pressed. When the pushbutton is released the action of command ends
o
Auto-maintained
: by pressing the or
pushbutton the command open or close is activated.
Even if the pushbutton is released the command remains active. It is reset by the pushbutton or if
the actuator reaches the end of travel.
H/PCU
:
Hydraulic
or
Pneumatic Control Unit:
made of Solenoid
Operated Valves,
hydraulic and pneumatic
valves, filter, directional
valves, etc. to drive the
Actuator in open and
close direction.