APT3200
Smart Pressure Transmitter
Operation Manual M3200-E01G
17
Duon System Co.,Ltd.
-
Change Lower Range Value
- Executing the menu to put Zero+Span button.
- Moving to the next menu to put Zero button when 1 TRIM message appear.
- Moving to the sub directory to put Span button when 2 Setup message appear.
- Moving to the next menu to put Zero button when 21 Unit message appear.
- Moving to the next menu to put Zero button when 22 Unit message appear.
- Executing the function to put Span button when 23 L-RNG message appear.
- The procedure of setting value is same as Zero Adjustment.
-
Decimal Place
- Executing the menu to put Zero+Span button.
- Moving to the next menu to put Zero button when 1 TRIM message appear.
- Moving to the next menu to put Zero button when 2 Setup message appear.
- Moving to the sub directory to put Span button when 3 LCD message appear.
- Executing the function to put Span button when 31 DEC-PL message appear.
When Decimal Place function excuted, the type of decimal place will be appear on the
secondline of LCD as below.
Display Explanation Max.
Value
Remark
AUTO
Target value will be displayed
automatically (Former Display Type)
99999
5-0
None decimal place
99999
4-1
Display one decimal place
9999.9
3-2
Display two decimal place
999.99
2-3
Display three decimal place
99.999
1-4
Display four decimal place
9.9999
- Firstly, 0.0 will be display on the first line of LCD.
- Decimal place will be change whenever put the Zero button. Saving the setting value to put
Span button after select the required decimal palce.
- The set value will be applicable for displaying PV value and Engineering value. 3-2 format will
be displayed for mA and % regardless any setting.
- LCD_OV message and current setting Unit will be displayed when over the LCD limitvalue.