APT3200
Smart Pressure Transmitter
Operation Manual M3200-E01G
41 Duon System Co.,Ltd.
Appendix I
APT3100 SMART PRESSURE TRANSMITTER
LCD DISPLAY CODE
Message Description
Remarks
ADJ-U
Out of Zero setting value when Zero Adj function using button(Upper
side)
ADJ-L
Out of Zero setting value when Zero Adj function using
button(Lower side)
ZERO
Innitial message in using Zero button
SPAN
Innitial message in using Span button
BT-ERR
Button input Sequence error
P-LOCK
Button input error when Protect Locked
ZT-ERR
Setting Limit(10%) Error when Zero Trim
-TR- Zero
Trim
Done
ZR-ERR
Setting Limit error when executing Zero button function
SP-ERR
Setting Limit error when executing Span button function
-ZR-
Zero button function done
-SP-
Span button function done
-ZA-
Zero Adjustment done
-DONE- Setting
Done using button
RNGOVR
Setting Limit error when executing other setting function
LCD_OV
Over figure values for LCD
SCD-ER Sensor
Code
Error
F-RST
Flash Setting Data Reset
F-LOCK
While Flash Setting Data Reset, Protect Locked
F-FAIL
Flash Setting Data Reset Failure
-FR- Flash
Reset
Done
A-RST
Analog EEPROM Initializing Start
A-STOR
Analog EEPROM Whole Write
A-FAIL
Analog EEPROM Whole Write Failure