Connect the fuel supply to the inlet of the fuel solenoid (see table
for recommended line size).  The pressure at the secondary
demand regulator must be four to six ounces psi (per square
inch) or 7 to 11 inches W.C. (Water column)  for vapor withdrawal
units.  On units equipped with liquid withdrawal fuel systems full
tank pressure is plumbed to the fuellock strainer mounted on the
generator rails.  The fuel converter mounted on the unit will
handle both vaporization of the fuel and pressure reduction.

INSTALLING THE FUEL LINE

** NOTICE **

The engine generator sets are properly adjusted before they
leave the factory for a specific fuel, either NG (natural gas), LP
(liquid  propane vapor) or LPG (liquid withdrawal propane).  This
fuel type is noted in your model number.  If it becomes necessary
to change the fuel type in the field see information on page 12.

Line Size (vapor system)

Unit location will determine the size of fuel line that is required to
supply the engine with a constant fuel pressure.  Refer to the
tables below for fuel line size, fuel consumption and recom-
mended tank size.  For distances of 25 feet and over, a two
regulator fuel system is recommended.  This is accomplished by
installing a primary regulator at the tank which will reduce the
tank pressure down to 10 to 15 lbs.  A secondary regulator is
installed to further reduce the fuel pressure to the required six (6)
oz operating pressure.  This secondary regulator must be at least
10 feet from the engine generator set.  Any closer installation will
require a larger line be installed to provide a fuel reservoir.   If this
is not done, the demand regulator on the unit and the pressure
regulator in the fuel line will interfere with each other.  When this
two (2) stage regulator system is used, a fuel line size of 3/4 to 1
inch is generally adequate for distances up to 300 feet from the
primary to the secondary regulator.  (Consult your local fuel
supplier for your exact requirements). The appropriate line size
from the table below is then installed from the secondary regula-
tor to the generator set.

    *************
*****  WARNING  ****
    *************

PERSONAL DANGER - Do not use galvanized pipe in fuel line
runs.  The galvanized coating can become eroded and flake off,
causing possible obstructions in the regulator or fuel valve.  The
results could range from inoperative engine start to hazardous
fuel leaks.

Size of pipe normally required for generators operating on
NATURAL/LP gas:

       up to 25 feet*              over 25 feet*

GR27G4

   1" pipe                   not recommended

GR40G4

   1" pipe             use a two regulator system

* Allow an additional 3 feet for each standard elbow.

 Do not use ‘street ells’ (restrictive).

****  CAUTION  ****

EQUIPMENT DAMAGE - Be careful when sealing gas line joints.
Excessive sealing compound can be drawn into the solenoid,
regulator or carburetor causing an engine malfunction.

FUEL PRESSURE (vapor system)

Correct fuel pressure cannot be stressed enough.  The most
common cause for inoperative systems is an inadequate or
incorrect fuel pressure.  Performance of the engine is in direct
relation to the correctness of the fuel system.  Shown below is a
block diagram of a typical L.P. or N.G. Installation.

 Supply

   Primary

 Secondary

Generator

  Tank

   Regulator

 Regulator

   Set

        1                  2

3

    4

TWO (2) REGULATOR FUEL SYSTEM

   Supply

       Primary

Generator

    Tank

Regulator

     Set

1

2

4

SINGLE REGULATOR FUEL SYSTEM

Reference numbers 1 through 3 in the block diagrams above are
fuel lines supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure readings at each reference in
the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only)

1

2

3

UNIT OFF

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

7-11 in

7-11 in

4-6 oz

 4-6 oz

FULL LOAD

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

Two (2) Regulator System (L.P. Vapor only)

1

2

3

4

UNIT OFF

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6oz

STARTING

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

Natural Gas

1

2

4

UNIT OFF

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

LINE PSI

7-11 in

 7-11 in

4-6 oz

4-6 oz

FULL LOAD

LINE PSI

7-11 in.

7-11 in

4-6 oz

4-6 oz

Содержание Winpower GR27G4 B Series

Страница 1: ...GR40G4 Engine Generator Set PACKAGE STANDBY SYSTEMS INSTALLATION AND OPERATIONS MANUAL GR27G4 B GR40G4 B ...

Страница 2: ... THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries Read and understand all instructions in the manual before starting and operating the generator set USING THIS MANUAL Congratulations on your choice of a Winpower genera tor set You have selected a high quality precision engi neered generator set...

Страница 3: ...d electrician or contractor The installation must comply with all national state and local codes g Always make sure unit is disabled before placing your hands anywhere near the fan belts alternator or water hoses IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTION This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries...

Страница 4: ...dustrial four cylinder liquid cooled engine equipped to run on L P N G fuel The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The 27 000 watt 27kW generator is a single bearing direct drive rotating field design The generator is connected to the engine flywheel via flexible drive disks The engine g...

Страница 5: ...t temperature battery voltage speed engine load coolant level from ECU ECU specific parameters and run time statistics A Liquid Crystal Display The backlit 64 by 128 pixel LCD serves as the local information source for metering alarms pre alarms and protective functions Display operation is maintained at 20 C An optional LCD heater maintains display operation at 40 C B Not in Auto Indicator This r...

Страница 6: ...esetting the system clock 1 Press K right key for initial set or K left to back up up down to choose menu item and time date element to be changed 2 Press L Edit to access change mode to enter Password OP as follows 2a Press K up to select O 2b Press K right to move cursor 2c Press K up to select P 2d Press L Edit to begin change mode 3 Press K up or down to choose year 4 Press L Edit to enter yea...

Страница 7: ...ould the instructions or information provided be interpreted to conflict with any local state or national codes If in doubt always consult your local fire marshal or gas supplier WARNING FIRE HAZARD All fuel runs should be installed by a licensed fuel supplier The engine manufacturer has established an excellent world wide engine service organization engine service is available from a nearby autho...

Страница 8: ...led from the secondary regula tor to the generator set WARNING PERSONAL DANGER Do not use galvanized pipe in fuel line runs The galvanized coating can become eroded and flake off causing possible obstructions in the regulator or fuel valve The results could range from inoperative engine start to hazardous fuel leaks Size of pipe normally required for generators operating on NATURAL LP gas up to 25...

Страница 9: ...rformed or supervised only by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When installing or replacing batteries use the proper group size starting battery The battery should be a Maintenance Free lead acid design Deep cycle batteries will not work for this applica tion CAUTION PERSONAL DANGER CAUTION NEVER dispose of a battery ...

Страница 10: ...olant temperature between 100 and 120 degrees F MOUNTING THE AUTOMATIC TRANSFER SWITCH A T S WARNING FIRE HAZARD All wiring must be done by a licensed electri cian and must conform to the national electrical code and comply with all state and local codes and regulations Check with the local authorities before proceeding INSTALLATION NOTES Because of the many different types of service feeder and d...

Страница 11: ...ed for you to connect your ground wire from the transfer switch to The lugs on the 40 kW will handle wire sizes 6 AWG to 250 MCM and should be torqued to 250 in lbs The lugs on the 27 kW will accommodate 6 AWG to 250 MCM and should be torqued to 250 in lbs WARNING A main line circuit breaker has been provided inside the genera tor housing During all wiring installations make sure the breaker is in...

Страница 12: ...mode until the remote start relay is closed again F CUSTOMER REMOTE STOP LIGHT This set of terminals can be use to light a 12 volt remote light to indicate that the unit is in emergency stop The terminal blocks are designed to use terminal lugs on all wires and the screws should be torqued to 9 6 in lbs G REMOTE DISPLAY PANEL INTERFACE TERMINALS These interface terminals are prewired to allow for ...

Страница 13: ...be certain of a balanced voltage output and a solid neutral connection The voltage between G1 and G N should be about 120 volts AC 277 on 480 units The same approximate voltage should be found between terminals G3 and G N 120 volts AC On three phase panels the G2 voltage level should also be checked ON 240 VOLT DELTA SYSTEMS BE SURE YOU KNOW WHERE THE HIGH VOLTAGE WILD LEG IS IT MUST BE IN THE SAM...

Страница 14: ...4 Defective start stop relay NO AC OUTPUT FROM GENERATOR 1 Defective diode 2 Defective voltage regulator 3 Defective rotor 4 Defective stator 5 Defective exciter rotor 6 Defective exciter stator 7 AC short in the output leads 8 Defective field circuit breaker NG LP CONVERSION CAUTION EQUIPMENT DAMAGE Do not make any fuel adjustments or governor adjustments until all pressure readings are in compli...

Страница 15: ...position As soon as the solenoid opens the pressure should rise to 2 5 to 3 oz just as the engine starts to crank If it is within this range replace the cap on the column If not adjust the screw down to increase and up to decrease and retest 8 Next the timing on the engine must be changed As this unit was shipped to operate on LP the timing advance was set at 26 degrees For operation on NG it will...

Страница 16: ...Page 14 7270 00 60708 141 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS ...

Страница 17: ...60708 141 Page 15 7270 00 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS ...

Страница 18: ...Page 16 7270 00 60708 141 ...

Страница 19: ...60708 141 Page 17 7270 00 GR40G4 GR27G4 OUTLINE DRAWING AND WIRING ENTRANCE DIMENSIONS ARE SUBJECT TO CHANGE ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSES ...

Страница 20: ...y and all warranties including those of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever accurs first from date of purchase In no event is WINPOWER liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or ...

Отзывы: