background image

Page 3

60706-133

8290-01

C. The foundation surface should be flat.

D. Space is required around the generator for mounting

switching devices, making connections, and for servicing.

E. The generator mounting backet must rest evenly and firmly

on the foundation. Install shims if necessary to even out
the foundation under the mounting pads then bolt the gen-
erator firmly in place.

TRAILER MOUNTING

Mount the generator on a trailer if you plan to use it as a
portable power source. See Figure 4. When selecting or
building a trailer to mount the generator, consider the follow-
ing points:

A. The trailer construction must be strong enough to support

the generator.

B. The design of the trailer must enable the trailer to remain

stable during operation, and to resist tipping caused by
generator starting and reflected load torque.

WARNING: Personal Injury & Equipment Damage
TRAILER MAY TIP OVER AND CAUSE INJURIES IF
WHEELS ARE NOT SPACED FAR ENOUGH APART
.

C. The trailer height and mounting position of the generator

on the trailer should enable aligning the drive shaft (tum-
bling bar) in a straight or nearly straight line between the
power take-off and generator input shafts. Misalignment
must be less than 15 degrees during generator operation,
even though the mechanical design of the tumbling bar
would allow greater misalignment.

D. The generator mounting area of the trailer bed should be

flat.

E. The generator mounting bracket must rest evenly and

firmly on the trailer bed. Install shims if necessary to even
out the bed under the mounting pads, then bolt the genera-
tor firmly in place.

5. Insert the brass pin (with cable) into the plug body, and

line up the retainer pin holes in the brass pin with those
in the plug body.

6. Insert the retainer pin, and tap it firmly into place. The

retainer pin will protrude approximately 3/8" when fully
seated. (See Figure 1.)

7. Repeat steps 4 through 6 for each brass pin. Make sure

to connect the neutral lead (cable), identified and color
coded in conformance with the applicable local electrical
codes, to the large diameter pin (“N”) on the plug.

WARNING: Electrical Shock

DURING THE NEXT STEP, THE LOAD DISCONNECT PLUG
SHOULD NOT BE PLUGGED INTO ITS RECEPTACLE.
ALSO, MAKE SURE THAT THE EQUIPMENT TO WHICH
THE PLUG LEADS (CABLES) ARE BEING CONNECTED IS
NOT ENERGIZED (LIVE).

8.

Strip the insulation off the free end of each of the plug

leads (cables), and connect them to the load transfer switch
(or directly to the load).

12PTOC-3

The only assembly work required after unpacking the
generator is to assemble and wire the load disconnect plug,
which is contained in the subpack carton packed in the
generator crate. This load disconnect plug is a Alpha type 4
wire locking plug.  The instruction for wiring the plug are in
the box with the plug.  The gauge wire required will depend
on the type of wire you buy.  You will need wire of sufficient
size to carry 50 amps at 240 volt.  Consult with your local
wire supplier for the proper gauge and type.

Installation

FOUNDATION MOUNTING

Mount the generator on a foundation if it is to be used as a
permanent or standby power source (see Figure 2). See
“TRAILER MOUNTING” if generator will be used as a
portable power source (see Figure 3). When planning a
foundation consider the following points:

A. The foundation location should enable aligning the drive

shaft (tumbling bar) in a straight or nearly straight line be-
tween the power take-off and the generator input shaft.
Misalignment must be less than 15 degrees during gen-
erator operation, even though the mechanical design of
the tumbling bar would allow greater misalignment.

B. The foundation must be solid enough to absorb genera-

tor starting and reflected load torque during operation.

Figure 2

Figure 3

Trailer, for Portable Operation

Содержание 64864011

Страница 1: ...60706 133 12PTOC 3 25PTOC 3 Tractor Drive PTO Generators OWNERS MANUAL INSTALLATION AND OPERATION INSTRUCTIONS SAFETY FIRST READ THIS MANUAL BEFORE OPERATING YOUR GENERATOR ...

Страница 2: ...terial or workmanship under normal standby use average less than 50 hours per month and service For warranty service return the product within 36 months from the date of purchase transportation charges prepaid to your nearest factory authorized service station or the WINCO factory There is no other express warranty To the extent permitted by law any and all warranties including those of merchantab...

Страница 3: ...sible explosion and or fire a Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas that must be mixed with fresh air a Operate only in well ventilated areas b Never operate indoors 4 NOISE HAZARD Excessive noise is not only tiring b...

Страница 4: ...isassembled in bag 5 Remove the four bolts which hold down the generator feet to the pallet 6 Lift the generator from the pallet by means of the lifting eye on the top of the generator 7 Inspect the generator carefully for freight loss or damage If loss or damage is noted at time of delivery require that the person making the delivery make note of the loss or damage on the freight bill or sign the...

Страница 5: ...ce The retainer pin will protrude approximately 3 8 when fully seated See Figure 1 7 Repeat steps 4 through 6 for each brass pin Make sure to connect the neutral lead cable identified and color coded in conformance with the applicable local electrical codes to the large diameter pin N on the plug WARNING Electrical Shock DURING THE NEXT STEP THE LOAD DISCONNECT PLUG SHOULD NOT BE PLUGGED INTO ITS ...

Страница 6: ...SONALINJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A SPECIAL DISCONNECT SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE DISCONNECT MUST ISOLATE THE GENERATOR FROM THE COMMERCIAL POWER LINES AND THE LOAD WHEN THE GENERATOR IS ON STANDBY AND MUST ISOLATE THE COMMERCIAL POWER LINES FROM THE LOAD AND THE GENERATOR WHEN THE GENERATOR IS SUPPLYING ...

Страница 7: ...motor not its starting current which is a lot higher Motor starting current requirements vary greatly by motor size and type Repulsion induction type motors are the easiest to start typically using 1 1 2 to 2 1 2 times as much current to start as to run capacitor type motors usually require 2 to 4 times as much current to start as to run split phase type motors are the hardest to start normally us...

Страница 8: ...HUTDOWNPROCEDURE 1 Switch off electrical load 2 Reduce speed of engine driving generator to idle 3 Disengage power take off drive and allow generator to coast to a stop WARNING Personal Injury Never try to manually stop the generator Always let it coast until it stops 5 Shut off the engine 4 Disconnect drive shaft tumbling bar power take off end first then generator end Figure 6 Figure 7 3 Make su...

Страница 9: ...nd generator mount ing hardware should be tight Clean and inspect the generator after storing it for long periods and after using it in extremely dusty conditions or in severe weather such as rain or blowing snow Lubrication The generator bearings are factory lubricated and sealed and require no further lubrication The generator input shaft should be cleaned and lubricated with a thin film of grea...

Страница 10: ...d of the armature are the generator output slip rings For proper generator output the surface of the slip rings must have a smooth shiny highly polished finish Normal brush seating will transfer a shiny black finish that will seat the copper surface This finish should not be removed unless it becomes dull or begins to build up Under sustained use it is advisable to check and if necessary polish th...

Страница 11: ...Either a high or low resistance reading will be obtained 7 Reverse the meter leads black lead to the DC NEG and red to the AC terminals each in turn An opposite reading should be observed 8 Check each terminal to the case An open circuit very high resistance reading should be observed A battery powered test light may be used Follow the same proce dures described above A good diode element will all...

Страница 12: ...ine if necessary 4 Incorrect field excitation 4 Check for worn brushes and weak or broken brush springs No load output low replace as required Check input AC voltage to rectifier Check rectifier output DC voltage to positive DC brush If no DC voltage is present at the brush replace the rectifier Check for dirty slip rings Clean them if they are dirty High voltage 1 Engine speed too fast 1 Check en...

Отзывы: