background image

Page 8

60706-133

8290-01

Proceed as follows:

1. Remove control box cover.  Vacuum or blow dust or de-

bris from the control box.  Inspect all wiring for correct
routing, fraying insulation, and secure connections.

2. Remove end cover. Vacuum or blow dust and debris from

the inside of the generator.  Inspect wiring for loose con-
nections, fraying insulation and correct wire routing.

3. Replace end cover and control box cover.

GENERATOR STORAGE

Before storing the generator, apply a heavy coat of grease to
the splined input shaft. Store the generator in a sheltered
area, where it is protected against snow, rain, and excessive
dust.

Generator Maintenance and Testing

A. Brushes

Under ordinary circumstances, brushes will operate for
extremely long periods without requiring replacement.  They
should be inspected after the first 500 hours of operation,
and after every 200 hours of operation thereafter.  Remove
brushes one at a time and check for length; be sure that each
moves freely in the brush holder.  Brushes should be
replaced when worn down to 3/8”.  Replace brushes in
complete sets, never singly.  When replacing brushes, be
careful to reconnect the lead wires properly.

Poor contact (or “skipping”) between brush and slip ring is
caused by oil and grit, flint, or other hard substance on the
brush, or by the brush not being properly shaped to fit the slip
rings.  Remedy these defects by fitting the brushes to the
slip-ring curvature.  Place # 00 sandpaper under the brushes
with the abrasive side to the brushes, and work it back and
forth until the brushes are the same shape as the slip-rings.

B. Slip rings

The four continuous copper rings located on the end of
the armature are the generator output slip rings.  For
proper generator output, the surface of the slip rings must
have a smooth, shiny, highly polished finish.  Normal
brush seating will transfer a shiny black finish that will
seat the copper surface.  This finish should not be
removed unless it becomes dull or begins to build up.
Under sustained use, it is advisable to check and if
necessary, polish the ring surfaces with a crocus cloth to
maintain the smooth finish.

C.

Electrical Testing

Testing generator fields for opens and grounds.

1. Disconnect field leads from rectifier.

2. Set multimeter to read resistance, and connect the meter

leads to the field leads.  If field is open, meter will read
infinite resistance (very high ohms).  Repair or  replace
field if it is open.  Typical resistance for these fields vary
from 20.2 TO 22.4 ohms.

3. Leaving one meter lead connected to the field, connect the

other meter lead to the field shell.  If meter indicates
continuity, any reading other  than infinite resistance,  the
field is grounded and should be repaired or replaced.  To
determine which of the fields is grounded, cut the connec-
tor between the two coils and retest  to determine which
coil has the low resistance path.

Testing the Armature for Opens and Grounds

1. Remove all brushes.

2. Ground fault test - set multimeter to read high resistance

(meg-ohms).Holding one meter lead against a clean spot
on the armature shaft, touch the other lead to each of the
slip rings (one at a time) while observing the meter.  If
meter indicates continuity (any reading lower than one
meg-ohm), the armature is grounded.  Dirt between the
slip rings and on the insulator surface can cause ground-
ing.  If grounding was indicated, carefully clean all dirt off
the slip rings and their insulators and then recheck it.  Re-
place the armature if it is grounded and unrepairable.

Содержание 64864011

Страница 1: ...60706 133 12PTOC 3 25PTOC 3 Tractor Drive PTO Generators OWNERS MANUAL INSTALLATION AND OPERATION INSTRUCTIONS SAFETY FIRST READ THIS MANUAL BEFORE OPERATING YOUR GENERATOR ...

Страница 2: ...terial or workmanship under normal standby use average less than 50 hours per month and service For warranty service return the product within 36 months from the date of purchase transportation charges prepaid to your nearest factory authorized service station or the WINCO factory There is no other express warranty To the extent permitted by law any and all warranties including those of merchantab...

Страница 3: ...sible explosion and or fire a Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas that must be mixed with fresh air a Operate only in well ventilated areas b Never operate indoors 4 NOISE HAZARD Excessive noise is not only tiring b...

Страница 4: ...isassembled in bag 5 Remove the four bolts which hold down the generator feet to the pallet 6 Lift the generator from the pallet by means of the lifting eye on the top of the generator 7 Inspect the generator carefully for freight loss or damage If loss or damage is noted at time of delivery require that the person making the delivery make note of the loss or damage on the freight bill or sign the...

Страница 5: ...ce The retainer pin will protrude approximately 3 8 when fully seated See Figure 1 7 Repeat steps 4 through 6 for each brass pin Make sure to connect the neutral lead cable identified and color coded in conformance with the applicable local electrical codes to the large diameter pin N on the plug WARNING Electrical Shock DURING THE NEXT STEP THE LOAD DISCONNECT PLUG SHOULD NOT BE PLUGGED INTO ITS ...

Страница 6: ...SONALINJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A SPECIAL DISCONNECT SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE DISCONNECT MUST ISOLATE THE GENERATOR FROM THE COMMERCIAL POWER LINES AND THE LOAD WHEN THE GENERATOR IS ON STANDBY AND MUST ISOLATE THE COMMERCIAL POWER LINES FROM THE LOAD AND THE GENERATOR WHEN THE GENERATOR IS SUPPLYING ...

Страница 7: ...motor not its starting current which is a lot higher Motor starting current requirements vary greatly by motor size and type Repulsion induction type motors are the easiest to start typically using 1 1 2 to 2 1 2 times as much current to start as to run capacitor type motors usually require 2 to 4 times as much current to start as to run split phase type motors are the hardest to start normally us...

Страница 8: ...HUTDOWNPROCEDURE 1 Switch off electrical load 2 Reduce speed of engine driving generator to idle 3 Disengage power take off drive and allow generator to coast to a stop WARNING Personal Injury Never try to manually stop the generator Always let it coast until it stops 5 Shut off the engine 4 Disconnect drive shaft tumbling bar power take off end first then generator end Figure 6 Figure 7 3 Make su...

Страница 9: ...nd generator mount ing hardware should be tight Clean and inspect the generator after storing it for long periods and after using it in extremely dusty conditions or in severe weather such as rain or blowing snow Lubrication The generator bearings are factory lubricated and sealed and require no further lubrication The generator input shaft should be cleaned and lubricated with a thin film of grea...

Страница 10: ...d of the armature are the generator output slip rings For proper generator output the surface of the slip rings must have a smooth shiny highly polished finish Normal brush seating will transfer a shiny black finish that will seat the copper surface This finish should not be removed unless it becomes dull or begins to build up Under sustained use it is advisable to check and if necessary polish th...

Страница 11: ...Either a high or low resistance reading will be obtained 7 Reverse the meter leads black lead to the DC NEG and red to the AC terminals each in turn An opposite reading should be observed 8 Check each terminal to the case An open circuit very high resistance reading should be observed A battery powered test light may be used Follow the same proce dures described above A good diode element will all...

Страница 12: ...ine if necessary 4 Incorrect field excitation 4 Check for worn brushes and weak or broken brush springs No load output low replace as required Check input AC voltage to rectifier Check rectifier output DC voltage to positive DC brush If no DC voltage is present at the brush replace the rectifier Check for dirty slip rings Clean them if they are dirty High voltage 1 Engine speed too fast 1 Check en...

Отзывы: