Operation
Page 67 of 100
057-230 ISSUE: 1
5.3.2
ENGINE RUNNING
NOTE: The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
Once the engine is running and all starting timers have expired, the animated
Engine Running
icon
is displayed.
In
Manual Mode
, the load is not transferr
ed to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources.
Press the
Transfer to Generator
button
Failure of mains supply (DSE6020 MKII only)
Activation of an auxiliary input that has been configured to
Remote Start On Load or Auxiliary
Mains Fail (
DSE6020 MKII Only
).
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
Once the generator has been placed on load, it is not automatically removed. To manually remove the
load either:
Press the
Open Generator
(DSE6010 MKII Only) or
Transfer to Mains
(DSE6020 MKII
Only) button
Press the
Auto Mode
button to return to automatic mode. The set observes all
Auto Mode
start requests and stopping timers before beginning the
Auto Mode Stopping
Sequence
.
Press the
Stop/Reset Mode
button to remove load and stop the generator.
Activation of an auxiliary input that has been configured to
Generator Load Inhibit.
5.3.3
STOPPING SEQUENCE
In
Manual Mode
the set does not continue to run until either:
The
Stop/Reset Mode
button is pressed
– The delayed load outputs are de-activated
immediately and the set immediately stops.
The
Auto Mode
button
is pressed. The set observes all
Auto Mode
start requests and
stopping timers before beginning the
Auto Mode Stopping Sequence
.
Содержание DSE6010 MKII
Страница 6: ...057 230 ISSUE 1 Page 6 of 100 11 1 WEEE WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT 98...
Страница 35: ...Installation Page 35 of 100 057 230 ISSUE 1 3 2 1 DSE6010 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE...
Страница 36: ...Installation 057 230 ISSUE 1 Page 36 of 100 3 2 2 DSE6020 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE...
Страница 37: ...Installation Page 37 of 100 057 230 ISSUE 1 3 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 3 3 1 GENERATOR...
Страница 38: ...Installation 057 230 ISSUE 1 Page 38 of 100 3 3 2 MAINS 6020 MKII ONLY...
Страница 99: ...This Page is Intentionally Left Blank...
Страница 100: ...This Page is Intentionally Left Blank...