Specification
057-230 ISSUE: 1
Page 26 of 100
2.13.7
ENCLOSURE CLASSIFICATIONS
2.13.7.1 IP CLASSIFICATIONS
The modules specification under BS EN 60529
Degrees of protection provided by enclosures
IP65
(Front of module when module is installed into the control panel with the optional sealing gasket).
IP42
(front of module when module is installed into the control panel WITHOUT being sealed to the panel)
First Digit
Second Digit
Protection against contact and ingress of solid objects
Protection against ingress of water
0
No protection
0
No protection
1
Protected against ingress solid objects with a
diameter of more than 50 mm. No protection
against deliberate access, e.g. with a hand, but
large surfaces of the body are prevented from
approach.
1
Protection against dripping water falling vertically. No
harmful effect must be produced (vertically falling drops).
2
Protected against penetration by solid objects with
a diameter of more than 12 mm. Fingers or similar
objects prevented from approach.
2
Protection against dripping water falling vertically. There
must be no harmful effect when the equipment (enclosure)
is tilted at an angle up to 15° from its normal position
(drops falling at an angle).
3
Protected against ingress of solid objects with a
diameter of more than 2.5 mm. Tools, wires etc.
with a thickness of more than 2.5 mm are
prevented from approach.
3
Protection against water falling at any angle up to 60° from
the vertical. There must be no harmful effect (spray
water).
4
Protected against ingress of solid objects with a
diameter of more than 1 mm. Tools, wires etc. with
a thickness of more than 1 mm are prevented from
approach.
4
Protection against water splashed against the equipment
(enclosure) from any direction. There must be no harmful
effect (splashing water).
5
Protected against harmful dust deposits. Ingress of
dust is not totally prevented but the dust must not
enter in sufficient quantity to interface with
satisfactory operation of the equipment. Complete
protection against contact.
5
Protection against water projected from a nozzle against
the equipment (enclosure) from any direction. There must
be no harmful effect (water jet).
6
Protection against ingress of dust (dust tight).
Complete protection against contact.
6
Protection against heavy seas or powerful water jets.
Water must not enter the equipment (enclosure) in
harmful quantities (splashing over).
Содержание DSE6010 MKII
Страница 6: ...057 230 ISSUE 1 Page 6 of 100 11 1 WEEE WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT 98...
Страница 35: ...Installation Page 35 of 100 057 230 ISSUE 1 3 2 1 DSE6010 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE...
Страница 36: ...Installation 057 230 ISSUE 1 Page 36 of 100 3 2 2 DSE6020 MKII TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE...
Страница 37: ...Installation Page 37 of 100 057 230 ISSUE 1 3 3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 3 3 1 GENERATOR...
Страница 38: ...Installation 057 230 ISSUE 1 Page 38 of 100 3 3 2 MAINS 6020 MKII ONLY...
Страница 99: ...This Page is Intentionally Left Blank...
Страница 100: ...This Page is Intentionally Left Blank...