11

[2]

System Times

Three system times are programmed in Section [2]; each time requires a 3-digit number.  Do not press the [#]
Key during data entry.

[1] Entry Delay

     (001 to 255 seconds)  The Entry Delay is the amount of time permitted between the activation

of a Delay Zone and the disarming of the system.  If the system is not disarmed during this delay, an alarm
will be generated.  Refer to Section [1] for information on which zone definitions are affected by the Entry
Delay.  The default Entry Delay is 30 seconds.

[2] Exit Delay

     (001 to 255 seconds)  The Exit Delay is the amount of time allowed to exit the premises after

an Access Code is entered to arm the system.  During the Exit Delay, a delay zone may be activated to
leave the premises; when the Exit Delay expires, the system will be armed.  Refer to Section [1] for
information on which zone definitions are affected by the Exit Delay.  The default Exit Delay is 120
seconds.

[3] Bell Cut-Off

     (001 to 255 minutes)  This time determines how long the bell/siren will sound when an alarm

is generated.  When an alarm is generated, the bell/siren will sound for this length of time, or until the alarm
is silenced by entering an Access Code.  The default setting is 4 minutes.

[3]

Installer’s Code

The default setting for the Installer’s Code is [0510].  It is strongly recommended that the Installer’s Code be
reprogrammed before installation is complete.  Be sure to record the new Installer’s Code for later reference.

[4]

Programmable Output Options (PGM1 and PGM2 Terminals)

The PGM outputs can be programmed to operate in response to various system operations.  The output pulse
connects the PGM terminal to the negative power rail.  Program two 1-digit numbers in Section [4].  The first
number entered determines how the PGM1 terminal will operate; the second number entered determines how
the PGM2 terminal will operate.

  Valid entries are from 1 to 9; do not enter 0.

[1]

Utility Output: 

When activated by entering [

][7], the PGM output switches to ground for 5 seconds and

the keypad buzzer will sound.

[2]

Keypad Sounder Follow Mode: 

The PGM output switches to ground as long as the keypad sounder is

ON.  The PGM output will 

not 

be activated when the keypad sounder beeps for acknowledgement tones

or for trouble indications.

[3]

Latched Alarm Output: 

The PGM switches to ground after any alarm (

other 

than [F], [A] or [P] Key

alarms) and remains switched to ground until an Access Code is entered or until the system is disarmed
using the keyswitch.  

An Access Code must be entered or the keyswitch must be operated to clear

the Latched Alarm Output, 

thus requiring the user to acknowledge an alarm.  This output can also be

used to indicate that an alarm has occurred before entering the premises.

[4]

Steady Alarm / [P] Key: 

The PGM output switches to ground when there is a burglar alarm, a 24-Hour

Steady alarm, or when the [P] Key is pressed.  The PGM output will be activated until the Bell Cut-off time
expires or until an Access Code is entered.

[5]

24-Hour Pulsed Alarm / [F] Key: 

The PGM output switches to ground when there is a 24-Hour Pulsed

alarm or when the [F] Key is pressed.  The PGM output will be activated until the Bell Cut-off time expires
or until an Access Code is entered.

[6]

[A] Key Alarm: 

The PGM output switches to ground when the [A] Key is pressed.  The PGM output will

remain activated until the Bell Cut-off time expires or until an Access Code is entered.

[7]

Trouble Output: 

The PGM output switches to ground when a Trouble condition occurs.  The PGM output

will remain activated until the trouble condition is corrected.

Содержание PC51O

Страница 1: ...N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully rea...

Страница 2: ......

Страница 3: ...splay Trouble Conditions 6 3 Display Alarm Memory 6 4 Bell Test 6 5 Master Code Program Access Codes 7 6 Door Chime On Off 7 7 Utility Output Command 7 8 Installer s Code Installer s Programming Comma...

Страница 4: ...nes are End of Line Resistor supervised Maximum zone loop resistance 100 ohms Bell Siren Output fused for 5A Bell Siren Alarms steady and pulsed alarms Programmable Output 50 mA with 9 options Auxilia...

Страница 5: ...ontrol panel Disassemble the keypad by pressing gently on the locking tab found on the bottom of the unit With the tab disengaged pull the backplate from the keypad Prepare a hole in the wall at the d...

Страница 6: ...attery The transformer should not be connected to an outlet that is controlled by a switch Battery Connection If the battery is connected in reverse the 5 A battery fuse will open and will need to be...

Страница 7: ...med when the Ready light is ON To arm the system enter a 4 digit Access Code As each digit is entered the keypad sounder will beep When the Access Code has been entered the Armed light will come ON an...

Страница 8: ...zones will come ON Ensure that any zone displayed as being bypassed is intentionally bypassed Zone bypasses are automatically cancelled when the system is disarmed To Bypass Zones Enter 1 Access Code...

Страница 9: ...instructions on restoring the system s factory default programming 6 Door Chime On Off The Door Chime feature causes the keypad to beep whenever a Delay or Instant Zone is activated This feature is u...

Страница 10: ...for 2 seconds to generate a P Key alarm This alarm may be programmed as either silent or audible refer to Programming Section 5 When programmed as audible the keypad will sound a series of short beeps...

Страница 11: ...or programming For 2 digit numbers both digits must be programmed before pressing the Key Only the data entered before pressing the Key will be changed When all data for a section is completely entere...

Страница 12: ...zone will also have the standard Entry Delay provided that a Delay Zone has been activated before the Interior Zone If an Interior zone is tripped before a Delay zone an alarm will be generated 3 Home...

Страница 13: ...two 1 digit numbers in Section 4 The first number entered determines how the PGM1 terminal will operate the second number entered determines how the PGM2 terminal will operate Valid entries are from...

Страница 14: ...default settings Notes on P Key Operation If the P Key is programmed as a silent alarm it is suggested that one of the Programmable Outputs be programmed with Option 3 Option 4 or Option 8 so that an...

Страница 15: ...__________________________ Phone ________________________ Name ________________________________ Phone ________________________ ZONE INFORMATION Zone Type Protected Area 1 ____________________ ________...

Страница 16: ...ogrammable Output 1 7 activates PGM 2 Keypad sounder follow mode 3 Latched alarm 4 Steady Alarm P Key 5 24 Hour Pulsed Alarm F Key 6 PGM activates on A Key alarm 7 PGM activates on Trouble alarm 8 PGM...

Страница 17: ...Z1 COM Z2 NC NO NC NC END OF LINE RESISTOR 5600 0 5W END OF LINE RESISTOR 5600 0 5W EOL RESISTOR LOOPS USING NO NC DEVICES EOL RESISTOR LOOPS USING NC DEVICES ONLY TRANSFORMER 16VAC 20VA MIN DO NOT CO...

Страница 18: ...determined and which may be revised from time to time will be charged for each unit repaired Products which Digital Security Controls Ltd determines not to be repairable will be replaced by the neares...

Страница 19: ...not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke detec...

Страница 20: ...1997 2002 Digital Security Controls Ltd Toronto Canada Printed in Canada 29000864 R1 1 800 387 3630...

Отзывы: