
4
When the transformer is plugged in there should be lights on the keypad and the buzzer connected to the bell terminals
may go ON for a few seconds. The “Armed” light may be ON or OFF the first time the panel is powered. The last armed/
disarmed condition is stored in the EEPROM memory so the panel will always power up in the last armed/disarmed
state. If the “Armed” light is ON, enter the default Master Code [1234] to disarm the panel. If the keypad is not active,
check for the presence of AC power at the “AC” terminals, check the keypad connections and check the panel fuses.
If all the zones are properly connected with double end of line resistors all of the Zone Lights will be OFF. Note that
the panel will arm only if all zones are properly connected with double end of line resistors so that the “Ready” light
is ON.
NOTE:
The Fire Zone only requires a single end-of-line resistor. The keypad should beep several times to
indicate acceptance of the Master Code. Enter the Master Code to arm or disarm the panel.
Read the “Keypad Functions” section of this manual or the “End User’s Manual” and enter commands on the keypad
to become familiar with the different commands.
Turn to the “Programming Guide” in this manual and enter a sample program into the panel through the keypad to
become familiar with the programming commands.
Mounting the Panel
Select a dry location close to an unswitched AC source, close to a ground connection and close to the telephone
connection.
Remove printed circuit board, mounting hardware and keypad from cardboard retainer inside panel. Before attaching
cabinet to wall, press the five white nylon printed circuit board mounting studs and the ground connection screw into
cabinet from the back.
Pull all cables into cabinet and prepare them for connection before mounting the circuit board to the back of the
cabinet. Press circuit board down onto mounting studs.
Hook-up Procedure
DO NOT connect transformer or battery until all other wiring has been connected. See power-up procedure.
Connect a ground cable from the cabinet ground connection by the shortest and most direct route to a grounding rod.
Connect zone cables to zone inputs and put double end of line resistors on any unused zones. Connect power wires
for motion detectors to the auxiliary supply.
Install keypads and connect wires to keypad terminals on panel. Connect RJ31-X cord to telephone terminals. Do not
insert plug into RJ31-X jack.
Connect bell or siren to “BELL [+]” and “BELL [-]” terminals. Observe correct polarity for sirens and polarized bells.
Connect 1000
Ω
½W resistor across terminals to eliminate trouble condition if bell circuit is not being used.
Terminal Connections
AC Power Terminals
Use a 16.5 VAC transformer with a minimum 40 VA rating to supply AC power to the PC2585. The transformer should
not be connected to an outlet that is controlled by a switch. If AC failure occurs it is displayed as a trouble on the keypad
(see “Keypad Functions, [
Q
][2] Trouble Conditions”). It can also be transmitted to the monitoring station as a trouble
condition (see “Programming Guide [
Q
][8]” sections [16] and [17] for alarm and restoral codes and Section [19] for
AC transmission delay).
Auxiliary Power Terminals: AUX+ and AUX-
Two “AUX” terminals are provided to ease wiring congestion at these terminals. The auxiliary power supply can be
used to power motion detectors and other devices requiring 12 VDC. 400mA 12 VDC is available from the “AUX+”
(positive) and “AUX-” (negative) terminals when the PC2585 is used with one keypad. For each additional keypad the
auxiliary supply rating must be reduced by 60mA. The auxiliary supply is fused with the keypad supply at 1 amp.
Auxiliary fuse failure can be transmitted (see [
Q
][8] sections [16] and [17]).
Switched Auxiliary Power Terminals: SW AUX and AUX-
The switched auxiliary supply can be switched off momentarily from the keypad (see “Keypad Functions [
Q
][4]”). The
“SW AUX” terminal is positive and the “AUX-” terminal negative. The 400 mA auxiliary supply rating must be reduced
by any current taken from the switched auxiliary supply. The switched supply shares the same fuse as the auxiliary
supply.
Bell/Siren Terminals BELL [+] and BELL [-]
These terminals are for powering bells or other devices requiring a steady output voltage on alarm. The bell output
is fused for 5 amps. When connecting sirens (speakers with siren driver already built-in), be sure to observe the correct
polarity. Connect the positive lead to the BELL [+] terminal and the negative lead to the BELL [-] terminal.
Содержание PC2585
Страница 55: ......