1
SPECIFICATIONS
Control Panel Specifications
12 zones including:
• 8 fully programmable supervised zones (EOL resistors)
including Fire Zone capability
• 1 auxiliary normally open zone
• 3 keypad activated zones
Audible alarm output:
• Bell output
• 700 mA, fused at 5 Amps, 12 VDC
• Steady or pulsed output
• Normal or inverted output
EEPROM memory:
• Does not lose codes or system status on complete AC
and battery failure
4 Programmable outputs:
• Transistor switch sinks 50 mA to ground. Operation
controllable through program options
• Powerful 1.5 amp regulated power supply:
• 400 mA auxiliary supply, 12 VDC
• Separately fused for battery, keypad/auxiliary supply
and bell output
• Supervision for loss of AC power, low battery
• Internal clock locked to AC power frequency
Switched Smoke Detector Supply Output:
• Controlled from keypad [
Q
][4] command
Battery required:
• 12 volt 4 Ah minimum rechargeable gel-cell or sealed
lead-acid battery
Transformer required:
• 16.5 VAC, 40VA
Dimensions:
• 11" × 11.8" × 3.3" deep (279 × 300 × 84 mm)
Weight:
• 6.5 lbs (3 kg)
Remote Keypad Specifications
(PC2550RK)
• Four wire (QUAD) hook-up
• Nominal current draw: 60 mA
• Up to 3 keypads per system (recommended). Maximum
5 keypads per system; refer to Keypad and Fire Circuit
Wiring Information
• Built-in piezoelectric buzzer
• Full annunciation of zones and system status
• Dimensions 5.5" × 4.5" × 1" deep
(140 × 114 × 25 mm)
Output Voltage Specification
Typically, with normal AC in and a fully charged battery,
the output voltage will be 13.8 VDC. With AC off and a
discharged battery, the voltage will go to 10 volts.
Devices that require power from the control panel should
be capable of normal operation over the voltage range
of 10 to 14 VDC.
Digital Communicator Specifications
• 92 reporting codes
• Transmits all 10 BPS and 20 BPS single line and
extended formats
• Radionics Rounds and Radionics Parity formats
• DTMF fast slot format
• 4/3 DTMF with Parity
• Pager Format
• Sescoa Superspeed formats
• Private Line format
• 3/1, 4/2 and hexadecimal numbers
• DTMF and Pulse dialing
• DPDT line seizure
• True dial tone detection
• Anti-jam feature
• 3 telephone numbers and 3 account codes
• Split reporting of selected transmissions to each
telephone number
Содержание PC2585