35
SIA Format
Level 2 (Hardcoded)
The SIA communication format used in this product follows the level 2 specifications of the SIA Digital Communication Standard
- February 1993. This format will send the Account Code along with its data transmission. At the receiver, the transmission would
look similar to this example:
N Ri01 BA 01
N = New Event
Ri01 = Partition / Area Identifier
BA = Burglary Alarm
01 = Zone 1
PC1580 Reporting Codes
SIA Identifiers &
Auto-Reporting Code
Delay Zone Alarm / Restore ................................... BA-XX / BH-XX*
Instant Zone Alarm / Restore ................................. BA-XX / BH-XX*
Interior Zone Alarm / Restore ................................. BA-XX / BH-XX*
Delay H.A. Zone Alarm / Restore ........................... BA-XX / BH-XX*
Interior H.A. Zone Alarm / Restore ........................ BA-XX / BH-XX*
24 Hr Burg Zone Alarm / Restore .......................... BA-XX / BH-XX*
Standard Fire Zone Alarm / Restore ...................... FA-XX / FH-XX*
Delayed Fire Zone Alarm / Restore ....................... FA-XX / FH-XX*
24 Hr Supervisory Buzzer Zone Alarm / Restore .. UA-XX/ UH-XX*
24 Hr Supervisory Zone Alarm / Restore ............. UA-XX / UH-XX*
24 Hr Medical Zone Alarm / Restore ................... MA-XX / MH-XX*
24 Hr Panic Zone Alarm / Restore ......................... PA-XX / PH-XX*
24 Hr Holdup Zone Alarm / Restore ..................... HA-XX / HH-XX*
24 Hr Gas Zone Alarm / Restore ........................... GA-XX / GH-XX*
24 Hr Heat Zone Alarm / Restore ........................... KA-XX / KH-XX*
24 Hr Emergency Zone Alarm / Restore .............. QA-XX / QH-XX*
24 Hr Sprinkler Zone Alarm / Restore .................... SA-XX / SH-XX*
24 Hr Water Zone Alarm / Restore ....................... WA-XX / WH-XX*
24 Hr Freeze Zone Alarm / Restore ....................... ZA-XX / ZH-XX*
24 Hr Latching Tamper Alarm / Restore ............... BA-XX / BH-XX*
Duress Alarm ........................................................................... HA-00
Opening After Alarm .............................................................. OR-00
Keypad Fire Alarm / Restore ..................................... FA-00 / FH-00
Keypad Auxiliary Alarm / Restore ........................... MA-00 / MH-00
Appendix B
S
I
A
V
F
O
R
M
A
T
PC1580 Reporting Codes
SIA Identifiers &
Auto-Reporting Code
Keypad Panic Alarm / Restore ................................. PA-00 / PH-00
Zone Tamper (1-6) ................................................................ TA-XX*
Zone Tamper Restorals (1-6) ............................................... TR-XX*
General System Tamper / Restore ........................... TA-00 / TR-00
Closing By Access Codes 1-6 ............................................... CL-XX
Partial Closing ................................................................... CG-XX
▼
Opening By Access Codes 1-6 ........................................ OP-XX
◆
Battery Trouble Alarm / Restore ............................... YT-00 / YR-00
AC Failure Trouble Alarm / Restore ......................... AT-00 / AR-00
Bell Circuit Trouble Alarm / Restore ......................... UT-99 / UJ-99
Fire Trouble Alarm / Restore ...................................... FT-00 / FJ-00
Auxiliary Power Supply Trouble Alarm / Restore .... YP-00 / YQ-00
TLM Trouble Code (via LINKS) ............................................... LT-00
General System Supervisory / Restore .................... ET-00 / ER-00
TLM Restoral ............................................................................ LR-00
FTC Restoral ............................................................................ YK-00
Event Buffer 75% Full Since Last Upload .............................. JL-00
Periodic Test Transmission .................................................... RP-00
System Test ............................................................................. RX-00
General Zone Fault Alarm/ Restore ........................ UT-00 / UJ-00*
Burglary Verified ...................................................................... BV-00
Closing Delinquent .................................................................. CD-00
* Zone Number is Identified
◆
User Number is Identified
▼
Each Zone Number is Identified (using UB-XX)