P R O G R A M  D E S C R I P T I O N S

[01] Ground Start Pulse

The PGM Output will activate for two seconds to obtain a dial
tone on Ground Start telephone equipment before the panel
attempts to dial. Two 2-second pauses should be inserted
at the beginning of the phone number when using this
option.

[02] Utility Output with any Access Code

The PGM output will activate for 5 seconds when the [

] [7]

[1] [Access Code] command is entered (see Section 3.0 –
“Keypad Commands”).

[03] Sensor Reset

The output will normally be active and switched to
ground.

This option is used to reset power for latching smoke
detectors. The output will deactivate for five seconds when
the [

] [7] [2] command is entered (see Section 3.4 – “[

] [7]

Output Functions”). The keypad buzzer will not sound for
the five second period.

Please refer to the Hook-Up diagram in this manual for
wiring instructions.

[04] Courtesy Pulse

Upon arming, the PGM output will activate for the duration
of the exit delay plus an additional two minutes. Upon entry,
the PGM output will activate for the duration of the entry
delay plus an additional two minutes.

[05] Keypad Buzzer Follower Mode

The PGM will activate when any of the following events
occur and will remain active for as long as the keypad
buzzer is active:
• Door Chime

• Entry Delay

• Auto-Arm Prealert

• Audible Exit Delay

• 24 Hour Supervisory Buzzer Zone

[06] System Armed Status

When the system is armed, the PGM output will switch to
ground at the beginning of the exit delay. The output goes
high (open) when the panel is disarmed.

[07] Latched System Event (Strobe Output)

The PGM output will switch to ground when any of the
system events (alarms) occur on the system. In the armed
state, the output will deactivate only when the system is
disarmed. If an alarm activates this output in the disarmed
state, the output will deactivate if the bell is silenced during
a bell time-out, or if the system is armed after the bell time-
out. This PGM output can be used to indicate that an alarm
has occured before entering the premises.
This output will activate for all audible alarms of the following
types:
Burglary ....... Delay, Instant, Interior, Stay/Away and

24 Hour Burglary Zones

Fire ............... Fire Keys, Fire Zone and Two-Wire Smoke

Zone (PGM Output)

Panic ............ Panic Keys and Panic
Medical ........ Auxiliary Keys, Medical and Emergency Zones
Supervisory . Supervisory, Freezer and Water Zones
Priority .......... Gas, Heat, Sprinkler and 24 Hour Latching

Zones

This output will activate for alarm conditions only.
Pre-alerts or delays will not activate the output. This

output should only be activated for all audible
alarms or medical conditions

[08] Failure to Communicate or Telephone Line

Monitoring Trouble

The PGM output switches to ground when either of the two
telephone line troubles are detected on the system (see
Section 3.4 – “[

] Commands; [

] [2] Trouble Conditions”).

The output will de-activate when neither trouble is present.

[09] Entry Delay Follower

The PGM output switches to ground for the duration of the
Entry Delay.

[10] Exit Delay Follower

The PGM output switches to ground for the duration of the
Exit Delay.

If this feature is used in conjunction with courtesy
pulse, it will terminate at the end of the courtesy
pulse time, not at the end of the exit delay.

[11] TLM and Alarm

The PGM output switches to ground when the system
experiences both a telephone line trouble and an alarm.
When the system is armed, the output will deactivate only if
an access code is entered. If the output is activated by an
alarm in the disarmed state, it will only deactivate if the bell
is silenced during bell time-out or if the system is armed after
the bell time-out.

This output will activate for all silent and audible
alarms except the Duress alarm.

[12] Police Code Follower

The PGM output switches to ground if two different zones go
into alarm during the same armed period. The Police Code
will be sent to the central station and this output will activate.
This output is latched.

[13] 20 Minute Latched Alarm

The PGM output will switch to ground upon an alarm and will
latch for 20 minutes or until disarmed. If activated while
disarmed, this output will be de-activated after 20 minutes or
if a code is entered during bell time out or if the panel is armed.

[14] Line Seizure

The output will switch to ground while the panel has seized
the telephone line for downloading purposes or to
communicate to the central station.

[15] Ready To Arm

The PGM switches to ground as long as the system is ready
to arm and all non-force armable zones on the system are
restored. Once an access code is entered to arm the system
and the exit delay begins, the PGM output is de-activated.

[17] Downlook Support

This option configures the PGM terminals for operation with
the DLM-1 or DLM-4 Video Capture module.

NOTE

Option 17 must be used on both PGM1 and PGM2 for

Downlook Support.  PGM1 connects to the DLM DTA and
the PGM2 connects to the DLM CLK.

Do not attempt to program PGM1 as any of the
remaining five input type options.

Содержание PC1580BABT

Страница 1: ...d Transmissions to Each Telephone Number System Introduction S E C T I O N 1 System Supervision Features The PC1580 continuously monitors a number of possible trouble conditions including AC Power Fai...

Страница 2: ...s as well as surveillance costs thus improving the overall security protection For more information regarding the Downlook Video Transmission Module please consult the DLM 1 DLM 4 Installation Manuals...

Страница 3: ...he various programmable features which options are available and how they function The Programming Worksheets pages 25 33 should be filled out completely before attempting to program the system Step 1...

Страница 4: ...estrictions apply to KEYBUS wiring KEYBUS should be run in minimum 22 gauge quad 0 5mm two pair twist is preferred The modules should be home run to the panel but can be connected in series or T tappe...

Страница 5: ...ons There are several different ways in which zones may be wired depending on which programming options have been selected Please refer to the following diagrams to study each type of individually sup...

Страница 6: ...MINIMUM 18 AWG WIRING IS REQUIR FOR RESIDENTIAL FIRE ALARM SYST TO ZONE Z TERMINAL PROGRAMMED FOR FIRE TO ANY COM TERMINAL A U X B E L L 1 P G M 2 2 8 5 Keyswitch Zone Wiring If PGM2 has been program...

Страница 7: ...ass interior zones manually When the system is armed using a valid user code if any zones on the system have been programmed as Stay Away zones the Bypass light will turn ON The panel will then monito...

Страница 8: ...ill be ON When using an LCD keypad the trouble conditions will be listed on the display the user must simply use the arrow keys to scroll through the list of present trouble conditions The various tro...

Страница 9: ...ccess code 1 One Master Code Access codes 2 to 6 Five User Codes All access codes have the ability to arm or disarm the system and can activate the PGM Outputs using the 7 1 Access Code and 7 2 comman...

Страница 10: ...e the arrow keys to scroll to the desired contrast level and press the key to exit Keypad Beeper Control The LCD keypad will allow you to select from 21 different keypad beeper tones Use the arrow key...

Страница 11: ...in Function Keys Section 3 5 05 9 No Entry Delay Arm Once this function key is pressed the user must enter a valid user code The system will arm and remove the entry delay from the system when the ex...

Страница 12: ...amming Decimal Data A set number of programming boxes are allotted for each section requiring decimal data e g codes telephone numbers If a digit is entered for each program box the panel will automat...

Страница 13: ...one Light 4 8 Add up the values for the zone lights to determine the number displayed for example no zone lights 0 all 4 zone lights 15 HEX F Press any of the Emergency Keys Fire Auxiliary or Panic to...

Страница 14: ...ll cause an instant alarm if it is violated when the panel is armed Typically this zone is used for windows patio doors or other perimeter zones 04 Interior Zone This zone will not cause an alarm if v...

Страница 15: ...hime This attribute determines whether or not the zone will activate the chime feature see Section 3 4 4 Door Chime On Off Bypass Enable This attribute determines whether or not the zone can be manual...

Страница 16: ...es The panel can be programmed to report events to the central station by sending the Reporting Code programmed for a particular event Reporting codes can be one or two digits and can use HEX digits A...

Страница 17: ...e Alarm Reporting Code during short power outages the panel will not send the signal unless AC power is lost for the amount of minutes programmed for the AC Failure Communication Delay The AC Failure...

Страница 18: ...rmats 1 The digit 0 will send no pulses and is used as a filler 2 When programming account numbers enter four digits When programming a three digit account number the fourth digit must be programmed a...

Страница 19: ...ing If the Downloading Answer option is enabled or during the first six hours after power up the panel will answer calls for downloading when the programmed Number of Rings is heard by the panel If th...

Страница 20: ...24 Hour Latching Zones This output will activate for alarm conditions only Pre alerts or delays will not activate the output This output should only be activated for all audible alarms or medical con...

Страница 21: ...porting Codes Section 44 TLM Trouble Delay Section 62 Option 1 5 12 Siren Supervision The panel supervises the Bell output If an open condition is detected or if the fuse is blown the panel will immed...

Страница 22: ...il the exit delay expires The keypad will beep rapidly for the last 10 seconds of exit delay to warn the user that the system is about to arm For commercial applications the Bell Squawk on Exit Delay...

Страница 23: ...eys are pressed for 30 seconds The keys however will remain backlit The panel will turn the lights back on when any key is pressed or when the entry delay begins or if an audible alarm occurs Keypad B...

Страница 24: ...following 1 Enter the Installer s Programming mode 2 Enter the appropriate programming section XY 3 Enter the Installer s Code 4 Re enter the appropriate programming section XY The panel will take a f...

Страница 25: ...eypad 3 I___________________________ __________________I I______________________________________ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Страница 26: ...I________I I________I I________I I________I KEYPAD 6 I________I________ I I________I I________I I________I I________I I________I KEYPAD 7 I________I________ I I________I I________I I________I I______...

Страница 27: ...Trouble Output 28 Silent 24 Hour PGM2 Only 09 Entry Delay Follower 29 Audible 24 Hour PGM2 Only 10 Exit Delay Follower 11 TLM and Alarm 12 Police Code Follower 07 Keypad Lockout Options Section 5 20 K...

Страница 28: ...Y Y N N Y Y Y Y Y Y Y Y Y Y N Option 3 Chime N Y Y Y N N N N N N N N N N N N N N N N N N N N Option 4 Force N N N N N Y Y N N N N N N N N N N N N N N N N Y Option 5 Bypass N Y Y Y Y Y Y N N Y Y N N N...

Страница 29: ...Codes I_______I_______ I Zone 1 I_______I_______ I Zone 4 I_______I_______ I Opening After Alarm I_______I_______ I Zone 2 I_______I_______ I Zone 5 I_______I_______ I Zone 3 I_______I_______ I Zone 6...

Страница 30: ...orting Codes Section 5 7 Communicator Reporting Codes I_______I_______ I Phone Number 1 Failure to Communicate I_______I_______ I General Zone Fault Alarm I_______I_______ I Phone Number 2 Failure to...

Страница 31: ...programmed 5 6 OFF I_______I 6 Restorals on Bell Time out Restorals Follow Zones 5 7 2 61 Second Communicator Option Code Default Option ON OFF Section OFF I_______I 1 Closing Confirmation Enabled Cl...

Страница 32: ...n 5 9 Downloading Default 1580 I_______I_______I______ _ I _ ______I Enter 4 Hexadecimal Digits 74 Panel Identification Code Section 5 9 Downloading Default 1580 I_______I_______I______ _ I _ ______I...

Страница 33: ..._______I 2 Handshake from Printer No Handshake OFF I________I 3 80 Column Printer 40 Column Printer OFF I________I 4 300 Baud Enabled Disabled OFF I________I 5 1200 Baud Enabled Disabled ON I________I...

Страница 34: ...cksum bad 3 A4 ROM checksum bad 3 A5 System Reset 3 A6 Panel prog changed 3 A7 Self test failure 3 A8 System Shutdown 3 A9 Battery Test Failure 3 1A Ground Fault Sounder Relay Troubles 3 2A Sounder Re...

Страница 35: ...XX 24 Hr Emergency Zone Alarm Restore QA XX QH XX 24 Hr Sprinkler Zone Alarm Restore SA XX SH XX 24 Hr Water Zone Alarm Restore WA XX WH XX 24 Hr Freeze Zone Alarm Restore ZA XX ZH XX 24 Hr Latching T...

Страница 36: ...nue from Step 2 until all Labels are programmed 01 to 06 Zone Labels 14 Characters Default to 33 Fire Alarm Label 14 Characters 34 System Label 14 Characters Default Default 40 Utility Output Label 14...

Страница 37: ...ys disabled OFF I_______ I 4 8 For Future Use 65 Fourth User Display Mask Default Option ON OFF ON I_______ I 1 User Initiated Call up Prompt ON User Initiated Call up Prompt OFF ON I_______ I 2 Last...

Страница 38: ...for persons with criminal intent to develop techniques which reduce the effectiveness these features It is important that a security system be reviewed periodically to ensure that its featu remain ef...

Страница 39: ...Panel Wiring Diagram TM Incorrect connections may result in fuse failure or improper operation Inspect wiring and ensure connections are correct before applying power Do not route any wiring over circ...

Страница 40: ...PROVED for connection to telecommunication systems specified in the instructions for use subject to the conditions set out in them S 5054 3 W 504203 DSC PC1580 REN 1 5 London office DSC Security Produ...

Страница 41: ...N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read...

Страница 42: ...the integral modem or call setup equipment to contravene the requirements of the standards for approval as designated All apparatus connected to this equipment and thereby connected directly or indire...

Страница 43: ...5 2 7 Removing Modules 5 2 8 Zone Wiring 5 2 8 1 Normally Closed NC Loops 5 2 8 2 Single End Of Line EOL Resistors 5600 5 2 8 3 Double End of Line DEOL Resistors 5 2 8 4 Fire Zone Wiring Four Wire Smo...

Страница 44: ...nd Sur Gard 4 8 1 Communications Format 18 5 8 2 Pulse Formats 18 5 8 3 Contact ID 18 5 8 4 SIA 18 5 8 5 Pager Format 19 5 9 Downloading 19 5 10 PGM Output Options 19 5 11 Telephone Line Monitor TLM 2...

Отзывы: