25
Appendix A: Table of Reporting Codes
The following tables contain automatic Contact ID and SIA format reporting codes. For more information on reporting formats,
see Section 4.3.5 “Communicator Format Options”.
Contact ID
The first digit (in parentheses) will automatically be sent by the control. The second two digits
are programmed to indicate specific information about the signal.
For example, if zone 1 is an fire zone point, you could program the event code as [1A]. The
central station would receive the following:
*FIRE* - FIRE ALARM - 1
where the “1” indicates which zone went into alarm.
SIA Format – Level 2
(Hardcoded)
The SIA communication format used in this product follows the Level 2 specifications of the SIA
Digital Communication Standard – October 1997. This format will send the account code along
with its data transmission. The transmission would look similar to the following at the receiver:
N Ri00 FA 01
N
= New Event
Ri00
= System Event
FA
= Fire Alarm
01
= Zone 1
Table 1: Automatic Contact ID/SIA Reporting Codes
*
Call directions: A/R = alarm/restoral; T/R = trouble/restoral; MA/R = maintenance alarm/restoral; S/R = supervisory/restore; T = test transmission
**
Line number/telephone number is identified (XX)
Section #
Reporting Code
Code Sent When…
Dialer
Direction*
Contact ID Auto
Rep Codes
Sia Auto Rep
Codes
[201] & [217]
Zone Supv./Rest.
zone goes into supervisory/ restore
S/R
(2) AA
See Table 3
[201] & [217]
Zone Alarms/Rest.
zone goes into alarm/ alarm condition has been restored
A/R
(1) 3A
See Table 3
[233] & [249]
Zone Trouble/Rest.
zone exhibits a trouble condition/ zone trouble condition
has been restored
T/R
(3) 73
See Table 3
[265] & [266]
AC Fail Trouble/Rest.
AC power to control panel is disconnected or inter-
rupted/AC power restored; both codes follow the AC
Trouble Delay
MA/R
(3) A1
AT-00/AR-00
[265] & [266]
Battery Trouble/Rest.
control panel battery is low/battery restored
MA/R
(3) A2
YT-00/YR-00
[265] & [266]
Ground Fault Trouble/
Rest.
Earth Ground Fault is detected/restored
MA/R
(3) 1A
UT-OO/UJ-00
[265] & [266]
NAC Trouble/Rest.
NAC circuit is opened/restored
MA/R
(3) 21
YA-99/YH-99
[265] & [266]
General System Trou-
ble/Rest.
module trouble is detected/restored
MA/R
(3) 3A
YX-00/YZ-00
[265] & [266]
Gen. System Supervi-
sory/Rest.
control panel loses/restores communications to enrolled
modules
MA/R
(3) 33
ET-00/ER-00
[265] & [266]
Secur-bus Trouble/
Rest.
Secur-bus connection is lost/restored
MA/R
(3) 33
NT-00/NR-00
[267] & [268]
Line 1 or 2 TLM Trou-
ble/Rest.
connection via Telephone Numbers 1 or 2 is lost/
restored
MA/R
(3) 51
LT-XX/LR-XX**
[267] & [268]
Phone # 1 or 2 FTC
Trouble/Rest.
communication is restored after a failure to communi-
cate trouble has occurred; events not communicated
during lapse will also be sent
MA/R
(3) 54
YC-XX/YK-
XX**
[269]
Walk Test Start/Stop
control panel has entered/exited walk test mode; no
events will be communicated
MA/R
(6) A7
TS-00/TE-00
[269]
Installer Lead In/Out
control panel enters/exits programming mode
MA/R
(6) 27/28
LB-00/LX-00
[269]
DLS Lead In/Out
remote computer connects/disconnects from the system
MA/R
(4) 12
RB-00/RS-00
[270]
Test Transmission
Normal/Off-Normal
test transmission reports system normal or off-normal
(alarm, supervisory or trouble) control panel condition
T
(6) A2
RP-00/RY-00