P
R O G R A M M I N G
T H E
C F P - 5 0 0
13
04 Supervisory
Classifies the zone as a fire supervisory. All alarms are instant and will turn on the buzzer
instead of the bell. Pressing the Trouble Silence Switch silences the supervisory buzzer. If a
Supervisory occurs while there is another zone alarm, the Signal Silence switch will silence
both the Alarm and Supervisory conditions. Silencing a Supervisory Alarm does not activate
the Signal Silenced trouble.
05 Four Wire Smoke (only) Auto Verify
Smoke detectors on that zone will be verified before an alarm is initiated. If this type of alarm
occurs with an alarm present on the system, or the auto-verify timer active, this zone will
become an instant alarm.
WARNING:
Manual Pull Stations MUST NOT be used on this zone type.
4.3.2 Panel System Option Code One [011]
[1] NAC1 Output Options
ON = NAC1 is Temporal. NAC1 will sound the Temporal/ANSI Fire Pattern of
0.5 seconds ON, 0.5 seconds Off, 0.5 seconds On, 0.5 seconds Off, 0.5
seconds On, 1.5 seconds Off, repeat.
OFF = NAC1 is Steady. NAC1 will stay on steady for an alarm condition.
[2] NAC2 Output Options
ON = NAC2 is Temporal. NAC2 will sound the Temporal/ANSI Fire Pattern of
0.5 seconds ON, 0.5 seconds Off, 0.5 seconds On, 0.5 seconds Off, 0.5
seconds On, 1.5 seconds Off, repeat.
OFF = NAC2 is Steady. NAC2 will stay on steady for an alarm condition.
[3] NAC Silence Options
ON = Automatic Signal Silence is Enabled. If enabled, the timer starts on the
first fire alarm and is restarted on subsequent fire alarms from other
zones. When the timer reaches 30 minutes from the last fire alarm, the
NAC’s are restored to normal. If after the panel has been silenced, either
manually or automatically, another alarm occurs it will restart the timer
for a full timing period.
OFF = Automatic Signal Silence is Disabled. The NAC’s will continue to sound
until the Signal Silence key is pressed.
[4] NAC2 Strobe Options
ON = NAC2 is a Strobe. NAC2 is restored to normal following a successful Sys-
tem Reset.
OFF = NAC2 is a Standard Bell. NAC2 is restored to normal following a Signal
Silence.
[5] Signal Silence Inhibit Options
ON = Signal Silence Inhibit Timer is Enabled. While in force, this timer pre-
vents manual signal silencing for 60 seconds. The timer is started on the
first alarm only and is not restarted on subsequent alarms. If after man-
ual or automatic silencing (no reset) a subsequent alarm occurs, the
Silence Inhibit timer is not started. This timer is only started on the first
fire alarm after a successful panel reset.
OFF = Signal Silence Inhibit Timer is Disabled. The Signal Silence key will
silence the alarm.
firealarmresources.com
Содержание CFP-500
Страница 31: ...firealarmresources com ...