background image

Tech Support: 1-800-387-3630 (Canada 
& US) or 905-760-30000 - www.dsc.com

2 9 0 0 9 0 6 8 R0 0 1

© 2014 Tyco International Ltd. and its Respective Companies. All Rights Reserved.
The  trademarks,  logos,  and  service  marks  displayed  on  this  document  are  registered  in  the  United  States  [or  other                

countries].  Any  misuse  of  the  trademarks  is  strictly  prohibited  and  Tyco  International  Ltd.  will  aggressively  enforce  its                

intellectual property rights to the fullest extent of the law, including pursuit of criminal prosecution wherever necessary.  All                

trademarks not owned by Tyco International Ltd. are the property of their respective owners, and are used with permission                

or allowed under applicable laws. 
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all                

products include all features. Availability varies by region; contact your sales representative.

Содержание 3G3070

Страница 1: ...CATOR INSTALLATION MANUAL V3 6 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The en...

Страница 2: ......

Страница 3: ...G3070 4 Status LEDS 5 Operating Principles 6 Simulated Landline Mode 6 Panel Transmission Monitoring PTM 6 Wireless Communications Sequence 6 Inputs 6 Outputs 7 Activating the Outputs 7 Swinger Shutdo...

Страница 4: ...user to Not attempt to service this product Opening or removing covers may expose the user to dangerous voltages or other risks Any servicing shall be referred to trained service persons only Use aut...

Страница 5: ...the control panel or provided by an external power supply rated for the application external power limited power source NOTE The power supply must be Class 2 Power Limited Ratings Power Supply Ratings...

Страница 6: ...g over circuit boards Maintain at least 1 25 4mm separation A mini mum 1 4 6 4mm of separation must be maintained at all points between Power Limited wiring and all other non Power Limited wiring Rout...

Страница 7: ...5 25 50 ANT 15ft 4 6m 25ft 7 6m or 50ft 15 2m are available The 3G3070 shall be powered from any compatible listed control unit or compatible listed power supply that complies with the ratings specifi...

Страница 8: ...building or structure and has been connected to the protective earth ground Descriptions of the terminals can be found in the Connecting the 3G3070 section 5 Reattach the front cover figure 1 item 1...

Страница 9: ...below The 3G3070 indicates the status of the highest priority unrestored trouble condition with the corresponding number of flashes of the red LED Once the highest priority trouble condition has been...

Страница 10: ...the 3G3070 restarts the error detection sequence before switching The 3G3070 performs this sequence on any phone number that is detected on the line Specific central station phone numbers can be prog...

Страница 11: ...it will not restore its state until all the causes of activation are cleared Contact ID Events Description Event Codes INPUT 1 ACTIVATION E110 FIRE ZONE 001 991 INPUT 1 RESTORAL R110 FIRE ZONE 001 99...

Страница 12: ...Programming Load option from the menu NOTE Uploading a defaulted communicator will generate an error in the 3G3070 software appli cation Downloading the Device Settings Once programming has been comp...

Страница 13: ...54 Failure To Communicate 000 FTC Restoral R 354 Failure To Communicate 000 Send over Cellular If this option is enabled this device will only communicate via cellular network effectively putting the...

Страница 14: ...el force dial feature if the control panel used with the 3G3070 does not force dial goes off hook but will not dial if there is no dial tone Status Page This page allows real time monitoring of all de...

Страница 15: ...must be active to ensure the signal strength displayed is that of the wireless network provider for which the SIM has access to Panel Programming the control panel should be programmed to communicate...

Страница 16: ...the power source connected to the 3G3070 is providing 13 8VDC 120mA and that the battery is fully charged Three Flashes Wireless Network Prob lem Ensure the SIM card has been activated The antenna cab...

Страница 17: ...he control panel has a central station phone number programmed Ensure the control panel has the correct account num ber programmed Verify the reporting codes are programmed or the auto Contact ID opti...

Страница 18: ...utdown for Telephone Line Monitor TLM transmissions for backup units If the 3G3070 is configured as a backup it can send a maximum of 3 TLM troubles and restorals per day TLM Swinger Shutdown only aff...

Страница 19: ...M 1 13 PGM 4 COM TAMPER 3G3070 PGM 3 DC IN NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NOT use a point that is normally used for 2 Wire Smoke dete...

Страница 20: ...ock washer Star washer Cabinet Alarm Control Panel with Dialler Interface Supports Contact ID format Panel Aux Power or External Power Supply 13 8V DC required for normal long term operation Telephone...

Страница 21: ...es to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DSC may...

Страница 22: ...d affect the operation of the equipment If this happens the Telephone Company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service Equipment M...

Страница 23: ...to adversely affect performance or prevent adequate inspection or testing to verify any war ranty claim Access cards or tags returned for replace ment under warranty will be credited or replaced at DS...

Страница 24: ...yco International Ltd will aggressively enforce its intellectual property rights to the fullest extent of the law including pursuit of criminal prosecution wherever necessary All trademarks not owned...

Отзывы: