15
3G3070 Wiring Diagrams
Figure 2Telephone Connection
RED (
R)
G
REEN (
T)
GR
A
Y (
R)
BRO
W
N (
T)
RJ-31X
RIN
G
TI
P
CONTROL PANEL
Incomin
g
Phone line
Hand
s
et
RI
TI
TI
RI
TI
P
RIN
G
4
3
2
1
5
3G3070
TIP
T1
R1
RNG
Figure 3 - Power Supply and Supervision Wiring Diagram
Control
Panel
EOL
Resistor
See Note 3
DSC
RM-2
RELA
Y
NC
C
NO
ZONE
TERMINALS
(See Note 1)
- +
+12VDC
GND
CONTROL PANEL
Aux Power
+ -
DSC
Supervision
Relay
See Note 2
19
18
17
16
14
20
15
12
11
10
9
7
13
8
6
19
Z4
Z3
Z2
COM
20
Z1
12
AUX
+
PGM
3
PGM
1
13
PGM
4
COM
TAMPER
3G3070
PGM
3
DC IN
+ -
NOTES
1.
Program the Zone/Point as “Supervisory” type
with keypad only annunciation when in Alarm.
Do
NOT use a point that is normally used for
2-Wire Smoke detectors.
2.
The power Supervision relay,
RM-2
is only used
when the 3G3070 is
not
powered by the control
panel. When the Radio is powered by the control
panel the relay is not required since a loss of input
power will generate a signal to the CMC.
3.
Output 4 on the 3G3070 must be set as “Active
High” (default).
4.
When powering the 3G3070 Radio by an
Auxiliary Power supply that has its own backup
battery, insert JP3 jumper on the radio and remove
the 1.2AH battery that came with the radio.