These inputs are normally open and will activate when a short condition is detected between the 
terminal and the COM.  Refer to the 3G3070 Wiring Diagram (Figure 4) at the back of this manual.

NOTE:  These inputs communicate using Contact ID format.

Outputs

The 3G3070 has four programmable outputs to activate in response to the associated events. Refer 
to the 3G3070 Wiring Diagram (Figure 4) at the back of this manual.

Activating the Outputs

The 3G3070 has four open collector outputs capable of a maximum of 50mA. Internal events on the 
3G3070 can trigger the outputs to turn on an LED or activate an input on the host panel. The default 
settings are as follows.

OUTPUT 1 Landline Trouble

 - Output is normally high and will switch to ground when the 

telephone line is down.

OUTPUT 2 Wireless Module or Network Trouble

 - Output is normally high and will switch to 

ground when the 3G3070 can not communicate with the 3G or 2G network.

OUTPUT 3 Power Supply or Battery Trouble

 - Output is normally high and will switch to ground 

when there is a problem with the power source.

OUTPUT 4 General Module Trouble

 -  Output is normally low and will switch to high when a 

Wireless Network Trouble, Power Supply/Battery Trouble, and/or a Failure to Communicate (FTC) 
trouble is detected.

NOTE: PGM4 must be connected to the control panel as shown in Figure 4 (Residential appli-
cations). Program the control panel input Zone/Point as 24hr ‘Supervisory’ with keypad-only 
notification when activated. Output 4 on the 3G3070 must be set as ‘Active High’.
NOTE: Once an output has been activated automatically, it will not restore its state until all the 
causes of activation are cleared.

Contact ID

Events Description 

Event Codes

INPUT 1 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E110 FIRE ZONE 001 991
INPUT 1 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .R110 FIRE ZONE 001 991
INPUT 2 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E120 PANIC ALARM ZONE 002 992
INPUT 2 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R120 PANIC ALARM ZONE 002 992
INPUT 3 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  E130 BURGLARY ZONE 003 993
INPUT 3 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R130 BURGLARY ZONE 003 993
INPUT 4 ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E300 SYSTEM TROUBLE ZONE 004 994
INPUT 4 RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  R300 SYSTEM TROUBLE ZONE 004 994
PSTN LINE DOWN:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  E351 TELCO 1 FAULT 000
PSTN LINE RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R351 TELCO 1 FAULT 000
12V INPUT LOSS:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E337 EXP. MOD. DC LOSS 000
12V INPUT RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  R337 EXP. MOD. DC LOSS 000
LOW BATTERY ALERT:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E338 EXP. MOD. LOW BAT 000
LOW BATTERY RESTORAL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R338 EXP. MOD. LOW BAT 000
PERIODIC REPORT: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E603 PERIODIC RF XMISSION 000
PERIODIC REPORT WITH OFF-NORMAL CONDITION:  . . .E608 PERIODIC TEST XMISSION SYSTEM TROUBLE PRESENT 000
3G UNIT ACTIVATION: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R552 RADIO XMITTER DISABLED 000
UNIT INTERNAL BUFFER FULL: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E624 EVENT LOG OVERFLOW 000
FTC RESTORAL:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R354 FAILURE TO COMMUNICATE 000

Swinger Shutdown

Swinger Shutdown is followed by a PSTN line trouble, limiting this event to a maximum of 3 trouble 
reports every 24 hours (including the PSTN line trouble sent when PTM is active). The condition will 
restore at midnight at which point the counter is reset.
NOTE: Swinger shutdown is applicable only to the radio-generated event codes listed above. Swinger 
shutdown on panel-generated events sent over the 3G3070 using dial capture is controlled by the 
panel settings.

Hardware Default

To perform a hardware default, follow these steps:
1. Ensure the unit is still powered down.
2. Connect a wire between PGM1 (terminal 7) and Z1 (terminal 15).
3. Power up the radio by connecting the battery first and then primary DC power.

Содержание 3G3070

Страница 1: ...CATOR INSTALLATION MANUAL V3 6 WARNING This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manu facturer The en...

Страница 2: ......

Страница 3: ...G3070 4 Status LEDS 5 Operating Principles 6 Simulated Landline Mode 6 Panel Transmission Monitoring PTM 6 Wireless Communications Sequence 6 Inputs 6 Outputs 7 Activating the Outputs 7 Swinger Shutdo...

Страница 4: ...user to Not attempt to service this product Opening or removing covers may expose the user to dangerous voltages or other risks Any servicing shall be referred to trained service persons only Use aut...

Страница 5: ...the control panel or provided by an external power supply rated for the application external power limited power source NOTE The power supply must be Class 2 Power Limited Ratings Power Supply Ratings...

Страница 6: ...g over circuit boards Maintain at least 1 25 4mm separation A mini mum 1 4 6 4mm of separation must be maintained at all points between Power Limited wiring and all other non Power Limited wiring Rout...

Страница 7: ...5 25 50 ANT 15ft 4 6m 25ft 7 6m or 50ft 15 2m are available The 3G3070 shall be powered from any compatible listed control unit or compatible listed power supply that complies with the ratings specifi...

Страница 8: ...building or structure and has been connected to the protective earth ground Descriptions of the terminals can be found in the Connecting the 3G3070 section 5 Reattach the front cover figure 1 item 1...

Страница 9: ...below The 3G3070 indicates the status of the highest priority unrestored trouble condition with the corresponding number of flashes of the red LED Once the highest priority trouble condition has been...

Страница 10: ...the 3G3070 restarts the error detection sequence before switching The 3G3070 performs this sequence on any phone number that is detected on the line Specific central station phone numbers can be prog...

Страница 11: ...it will not restore its state until all the causes of activation are cleared Contact ID Events Description Event Codes INPUT 1 ACTIVATION E110 FIRE ZONE 001 991 INPUT 1 RESTORAL R110 FIRE ZONE 001 99...

Страница 12: ...Programming Load option from the menu NOTE Uploading a defaulted communicator will generate an error in the 3G3070 software appli cation Downloading the Device Settings Once programming has been comp...

Страница 13: ...54 Failure To Communicate 000 FTC Restoral R 354 Failure To Communicate 000 Send over Cellular If this option is enabled this device will only communicate via cellular network effectively putting the...

Страница 14: ...el force dial feature if the control panel used with the 3G3070 does not force dial goes off hook but will not dial if there is no dial tone Status Page This page allows real time monitoring of all de...

Страница 15: ...must be active to ensure the signal strength displayed is that of the wireless network provider for which the SIM has access to Panel Programming the control panel should be programmed to communicate...

Страница 16: ...the power source connected to the 3G3070 is providing 13 8VDC 120mA and that the battery is fully charged Three Flashes Wireless Network Prob lem Ensure the SIM card has been activated The antenna cab...

Страница 17: ...he control panel has a central station phone number programmed Ensure the control panel has the correct account num ber programmed Verify the reporting codes are programmed or the auto Contact ID opti...

Страница 18: ...utdown for Telephone Line Monitor TLM transmissions for backup units If the 3G3070 is configured as a backup it can send a maximum of 3 TLM troubles and restorals per day TLM Swinger Shutdown only aff...

Страница 19: ...M 1 13 PGM 4 COM TAMPER 3G3070 PGM 3 DC IN NOTES 1 Program the Zone Point as Supervisory type with keypad only annunciation when in Alarm Do NOT use a point that is normally used for 2 Wire Smoke dete...

Страница 20: ...ock washer Star washer Cabinet Alarm Control Panel with Dialler Interface Supports Contact ID format Panel Aux Power or External Power Supply 13 8V DC required for normal long term operation Telephone...

Страница 21: ...es to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other rights DSC may...

Страница 22: ...d affect the operation of the equipment If this happens the Telephone Company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service Equipment M...

Страница 23: ...to adversely affect performance or prevent adequate inspection or testing to verify any war ranty claim Access cards or tags returned for replace ment under warranty will be credited or replaced at DS...

Страница 24: ...yco International Ltd will aggressively enforce its intellectual property rights to the fullest extent of the law including pursuit of criminal prosecution wherever necessary All trademarks not owned...

Отзывы: