17
[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised
Default (OFF)
(
TL2553G
only).
ON
: Ethernet Receiver 1 will be supervised and heartbeats will be sent to Ethernet
Receiver 1 based on the supervision interval programmed in Section [004].
OFF
: Ethernet Receiver 1 will not be supervised. When disabled, heartbeat 1 is sent
to the Ethernet receiver once every hour, regardless of supervision type (heartbeat 1
or 2). The heartbeat is resent every 5 seconds until ACK. If no event or heartbeat ACK
is received after (Receiver Supervision In 75 seconds), Supervisory trouble is
indicated.
NOTE: Ethernet Receiver 2 can not be supervised.
[2] Cellular Receiver 1 Supervised
Default (OFF)
ON
: Cellular Receiver 1 will be supervised and heartbeats will be sent to Cellular
Receiver 1 based on the supervision interval programmed in Section [004]. If ACK to
heartbeat is not received, it is retransmitted every 5 seconds. Failure to ACK 2
consecutive heartbeats will reset the radio.
OFF
: Cellular Receiver 1 will not be supervised. When disabled, heartbeat is not sent
to the receiver. Supervisory trouble is indicated.
NOTE: Cellular Receiver 2 can not be supervised.
[3] Supervision Type
Default (OFF)
ON
: Heartbeat 1 (Commercial Supervision). This supervision type is suitable for
applications where swap detection is required on the supervisory packet.
OFF
: Heartbeat 2 (Residential Supervision). This supervision type is suitable for
applications where supervision of the communication path to the receiver is required.
(no swap detection).
NOTE: Commercial supervision is more data intensive than residential supervision
and should only be used when required to meet the approval for the installation.
[4]
Primary Path
Default (OFF -
TL2553G
) (ON -
3G2055
)
ON
: Cellular channel is the primary path. Ethernet channel is the secondary path, if it
exists.
OFF
: Ethernet channel is the primary path in a dual Communicator. Cellular channel is
the secondary path.
[5] Redundant Communications
Default (OFF) (
TL2553G
only)
ON
: Events will be communicated to Ethernet Receiver 1 and Cellular Receiver 1 at
the same time. Events will be communicated to Ethernet Receiver 2 and Cellular
Receiver 2 at the same time. As long as the event is successfully communicated to 1
of the 2 paths (Ethernet or Cellular) the Communicator will move on to the next
event.
NOTE: Do not configure Ethernet Receiver 1 and Cellular Receiver 1 to communicate
using a common receiver configuration (i.e., identical Receiver IP address and
Receiver Remote Port).
OFF
: Events will be communicated to the receivers
individually.Toggle should be OFF when guaranteed message delivery to both receivers is
required.
[6]
Remote Firmware Upgrade
Default (ON)
ON
: The Communicator module firmware can be remotely upgraded using the
Ethernet/Cellular paths.
OFF
: The Communicator module firmware can not be remotely upgraded. Local
firmware upgrade is still possible.