Page | 65
Dryer Master DM510
Operations Manual
Control Limits:
•
Press the
‘arrow’
keys to highlight the
selection. Type in the
‘value’
followed by
the
‘Enter’
key
•
Press
‘Cancel’
to return to the
‘Previous
Menu’
.
Note:
The Control Limits are CRITICAL for proper system operation. Review and adjust as required.
Max Discharge rate in Auto
This is the maximum discharge or unload rate that can be set by the
DM510 Dryer Master. Set this value to a reasonable maximum that will
not compromise safe Dryer operation. When setting this value ensure the
conveying system is able to manage the volume of product.
Min Discharge rate in Auto
This is the minimum discharge or unload rate that can be set by the
DM510 Dryer Master. Set this value to a reasonable minimum that will
not compromise safe Dryer operation.
Discharge Off Rate
The DM510 Dryer Master uses this value along with drying temperature to
determine the dryer state. Set this value to slightly less than the
‘Minimum Discharge rate in Auto’ value.
Control will be severely
compromised if this value is set so that the DM510 does not obtain an
OFF indication.
Burner Off Temperature
The DM510 Dryer Master uses this value along with discharge or unload
rate to determine the dryer state. Set this to a value greater than the
maximum expected ambient temperature but less than the minimum
drying temperature. Control will be severely compromised if this value is
set so that the DM510 does not obtain an OFF indication.
Auto Fast Start
In normal operation the DM510 Dryer Master determines when it is ready
for Automatic operation. This process can take from a few minutes to a
dryer load or more. The Auto Fast Start feature bypasses the DM510
feature that determines stable operation. With Auto fast start the DM510
Dryer Master can be placed into Automatic before the ‘Ready light’ is
illuminated. A warning message with instructions will be displayed when
selecting Automatic before the ‘Ready light’ is illuminated.
Control Limits
Use keys to highlight your choice.
Enter a new value, then press ENTER.
Press CANCEL to exit.
Max Discharge rate in Auto
Min Discharge rate in Auto
,
Discharge Off Rate
Burner Off Temperature
100.0
7.0
5.0
110.0
Auto Fast Start (safety delay overide)
0 = Normal, 1 = Fast Start
0
Figure 74 - Settings (Supervisor Setup) Control
Limits menu