Diagnostics Screen 1:
•
Press the
‘Down arrow’
key to select
‘Diagnostics Screen 2’
•
Press the
‘Up arrow’
key for previous
screen
•
Press
‘Cancel’
to return to the
‘Main
Operations Screen’
.
Diagnostics Screen 2:
•
Press the
‘Down arrow’
key to select
‘Diagnostics Screen 3’
•
Press the
‘Up arrow’
key to select ‘
the
previous screen
•
Press
‘Cancel’
to return to the
‘Main
Operations Screen’
Inlet Sensor Signal
0-10 Vdc signal from sensor. 0.5 to 0.8 is typical empty voltage.
Greater than 9.50 Vdc is either extremely wet or damaged sensor.
Inlet sensor Temperature
Temperature as read by the inlet sensor temperature probe.
Outlet Sensor 1 Signal
0-10 Vdc signal from sensor. 0.5 to 0.8 is typical empty voltage.
Greater than 9.50 Vdc is either extremely wet or damaged sensor.
Outlet sensor 1
Temperature
Temperature as read by Outlet sensor1 temperature probe.
Outlet Sensor 2 Signal
Only present on systems with 2 outlet sensors. 0-10 Vdc signal
from sensor. 0.5 to 0.8 is typical empty voltage. Greater than 9.50
Vdc is either extremely wet or damaged sensor.
Outlet sensor 2
Temperature
Only present on systems with 2 outlet sensors. Temperature as
read by Outlet sensor 2 temperature probe.
Discharge Rate Input
Calibrated rate. Same as on main screen
Discharge Rate Output
Signal Dryer Master sends to dryer to run at the requested speed.
Should be equal to
Discharge Rate Input
.
Calculated Residence
Time, in seconds
Calculation is based on dryer volumes and throughput and the
current running speed.
Figure 66 - Support System Diagnostics Screen 1
Figure 67- Support System Diagnostics Screen 2
Diagnostics Screen 1
CANCEL = exit, Up = prev, Down = next
Inlet Sensor Signal
6.09
Vdc
Inlet Sensor Temperature
96.8
°
Outlet Sensor 1 Signal
3.13
Vdc
Outlet Sensor 1 Temperature
88.2
°
Outlet Sensor 2 Signal
0.00
Vdc
Outlet Sensor 2 Temperature
0.00
°
Discharge Rate Input
38.28
Discharge Rate Output
38.22
Calculated Residence time
5642.8
sec
Diagnostics Screen 2
CANCEL = exit, Up = prev, Down = next
Inlet Calibration Button
0
Outlet 1 Calibration Button
0
Outlet 2 Calibration Button
0
Local Remote Override
0
Dryer Fan Status
0
Dryer Discharge
1
Dryer Burner Status
1
Dryer Full Status
1
Mode Select
-1