MCS – MicroMag Error / Alarm Manual
Version: 02/21/2020
This alarm will trip if the Flow Switch on the
evaporator detects no flow for the allotted amount
of time (Setpoint 120). With this alarm tripped, the
compressors will each shut down until flow is
reestablished.
Note: Supervisor password (2112) is
required to reset lockouts
MicroMag Alarms
Possible Causes
Solutions
Flow switch is not
reading
The flow switch (top photo) is out of
adjustment. Isolate, then remove from
the pipe and clean sensor
Air is present in the chilled fluid lines.
Purge air from the system
No fluid in the tank or low fluid levels
Ensure y-strainer (bottom photo) and
process plumbing are free of blockages
or restrictions, and that all ball valves are
opened
Check for a loose wire on flow sensor
terminal block, and check that MicroMag
is outputting 5VDC
Pump not operating
correctly
Verify pump is running
Check for any blown fuses (left photo)
Verify that the overload relay has not
been tripped (right photo, reset button
circled)
Check pump phasing to ensure it is
rotating in the proper direction
No Flow