52
System Alarms
11.14
See "Display Mapping" in the Reference Section for a complete description of system alarms.
The Provisioning > System Alarms menu
Editing System Alarms
Pnt (Point)
The system alarm point number
Description
Non-editable description for this System (housekeeping) Alarm.
Silence
Check this box to choose to silence this alarm.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm
notifications for that alarm point.
BAU Global Settings
11.15
Building Access Unit Mode (BAU):
In this mode of operation access to the site is granted by issuing an OPR command to Display 1 point 54
"Extended Propped Door Mode". If access to the facility has not been granted using this method and a door is
opened, a door warning period will begin, followed by a door violation.
Clearing the Door Violation alarm:
·
Sending an OPR command to Display 1, Point 54 from T/Mon will enter "Extended Propped Door
Mode" and will suppress the speaker sounding under an alarm condition. The OPR command will also
clear a “Door Violation” alarm status. To cancel this mode send a RLS command from T/Mon to
Display 1, Point 54.
·
Sending a MOM command to Display 1, Point 54 from T/Mon will clear a Door Violation Alarm Status