Basic Analog Configuration
ID
Analog ID number.
Enab
Check this box to enable the analog.
Description
User-definable description for the analog channel.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Rev.
Reverse the polarity of the analog reading.
Advanced Analog Configuration (Details>>)
Record Freq
The amount of time, in minutes (min) or seconds (s), between each log of each
analog value to history.
Deadband
The amount (in volts) that the channel needs to go above or below a threshold in order
to cause an alarm.
Qual. Time
The length of thime that must pass, without interruption, in order for the condition to
be considered an Alarm or a Clear.
Qual Type
Allows you to choose whether you want to apply the Qualification Time to the alarm -
Set, Clear, or Both.
Units
User-definable display units or optional choice between Fahrenheit and Celsius
temperatures. The most common are:
VDC = Voltage
%H = Humidity
F = Fahrenheit
C = Celsius
Low Ref
User-definable lower reference/scaling level. This scales the information collected by
the sensor (in mA or VDC) to a meaningful unit for the user. For example, for a
temperature sensor, the lower input collected by the sensor may be 4mA (for a 4-
20mA sensor), which would correspond to a specific temperature you define in this
field.
High Ref
User-definable upper reference/scaling level. This scales the information collected by
the sensor (in mA or VDC) to a meaningful unit for the user. For example, for a
temperature sensor, the upper input collected by the sensor may be 20mA (for a 4-
20mA sensor), which would correspond to a specific temperature you define in this
field.
Thresholds
These settings are set to indicate the severity of the alarm depending on which
threshold values have been passed. Enter values for Major Under (MjU), Minor Under
(MnU), Minor Over (MnO), and Major Over (MjO).
Push-to-Talk: Enable
Checking this box enables Push-to-Talk feature for this analog.
Push-to-Talk: Discrete
Input
Assign the alarm point associated with this analog.
Push-to-Talk: Qual. Time
(ms)
Length of time, in milliseconds, that an alarm point must be set before an analog can
post.
Analog Gauge Type
Select the color-coded gauge that best represents your data. Selecting
None
will
disable the analog gauge and only a numerical representation of the value will be
displayed under
Monitor
>
Analogs
.