64
Display
Description
Port Address
Point
Display 16
Digital Temp Sensor 13 Minor Under
99
1
1
Digital Temp Sensor 13 Minor Over
99
1
2
Digital Temp Sensor 13 Major Under
99
1
3
Digital Temp Sensor 13 Major Over
99
1
4
Digital Temp Sensor 13 - Sensor not detected
99
1
5
Control
99
1
9-16
Value*
99
1
17-32
Display 17
Digital Temp Sensor 14 Minor Under
99
1
1
Digital Temp Sensor 14 Minor Over
99
1
2
Digital Temp Sensor 14 Major Under
99
1
3
Digital Temp Sensor 14 Major Over
99
1
4
Digital Temp Sensor 14 - Sensor not detected
99
1
5
Control
99
1
9-16
Value*
99
1
17-32
Display 18
Digital Temp Sensor 15 Minor Under
99
1
1
Digital Temp Sensor 15 Minor Over
99
1
2
Digital Temp Sensor 15 Major Under
99
1
3
Digital Temp Sensor 15 Major Over
99
1
4
Digital Temp Sensor 15 - Sensor not detected
99
1
5
Control
99
1
9-16
Value*
99
1
17-32
Display 19
Digital Temp Sensor 16 Minor Under
99
1
1
Digital Temp Sensor 16 Minor Over
99
1
2
Digital Temp Sensor 16 Major Under
99
1
3
Digital Temp Sensor 16 Major Over
99
1
4
Digital Temp Sensor 16 - Sensor not detected
99
1
5
Control
99
1
9-16
Value*
99
1
17-32
Display 20
Expansion 1 Alarms 1-64
99
1
1-64
Display 21
Expansion 1 Controls 1-16
99
1
1-16
Undefined
99
1
17-64
*Note: "Digital Temp Sensor Value*" must be multiplied by the appropriate VBIT from table 14.2 in order to create a displayable Value*.
Display Mapping
System Alarms
14.3
Display Points
Alarm Point
Description
Solution
2
33
Unit reset
Unit has rebooted.
If unintentional, call DPS Tech Support:
(559) 454-1600.
34
NTP Failed
Communication with Network Time Server
has failed.
Try pinging the Network Time Server’s IP
Address as it is configured. If the ping test
is successful, then check the port setting
and verify the port is not being blocked on
your network.
35
Timed Tick
Toggles state at constant rate as
configured by the Timed Tick timer
variable. Useful in testing integrity of
SNMP trap alarm reporting.
To turn the feature off, set the Timed Tick
timer to 0.
36
Serial 1 RcvQ
full
Serial port 1 (or appropriate serial port
number) receiver filled with 8 K of data (4
Check proxy connection. The serial port
data may not be getting collected as
Содержание D-PK-NG432
Страница 10: ...6 NetGuardian Front Panel 5 NetGuardian 432 G3 NetGuardian 432 G4 NetGuardian 480 G3 NetGuardian 480 G4 ...
Страница 50: ...46 Modbus Devices 10 12 The Provisioning Modbus Devices ...
Страница 52: ...48 Modbus Registers 10 13 The Provisioning Modbus Registers ...
Страница 75: ...71 ...
Страница 77: ...73 ...
Страница 78: ......