Alarms
10.8
Discrete alarms are configured from the
Provisioning
>
Alarms
and
Provisioning > Exp. Alarms
menus.
Descriptions for the alarm points, polarity (normal or reversed) and notification type(s) are defined from this menu.
You also have the option to use
Basic
or
Advanced
configuration methods, explained in this section.
The Provisioning > Alarms menu
The Provisioning > Exp. Alarms menu (NetGuardian 480 only)
Basic Alarm Configuration
ID
Alarm ID number.
Description
User-definable description for the discrete alarm point.
Rev (Reverse)
Reverse: Check this box to reverse the polarity of the alarm point. Leaving this option
un-checked means a normally open contact closure is an alarm. When polarity is
reversed, a normally closed alarm point is clear when closed.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm notifications
for that alarm point.
Advanced Alarm Configuration (Advanced>>)
On Set
User-definable description (condition) that will appear for the discrete alarm input on
Set. Example: "Alarm".
On Clear
User-definable description (condition) that will appear for the discrete alarm input on
Clear: "Example: "Alarm Cleared".
Qual. Time (Qualification
Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Qual. Type (Qualification
Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm
Set, Clear, or Both.
Содержание D-PK-NG432
Страница 10: ...6 NetGuardian Front Panel 5 NetGuardian 432 G3 NetGuardian 432 G4 NetGuardian 480 G3 NetGuardian 480 G4 ...
Страница 50: ...46 Modbus Devices 10 12 The Provisioning Modbus Devices ...
Страница 52: ...48 Modbus Registers 10 13 The Provisioning Modbus Registers ...
Страница 75: ...71 ...
Страница 77: ...73 ...
Страница 78: ......