10.10.1
HVAC Monitoring
Temperature / Air Flow sensors can be used to monitor HVAC health. Enabling HVAC Monitoring on this sensor
adds the extra fields below.
Sensor with HVAC Monitoring enabled.
HVAC Monitor Mode
HVAC Start Time
The time the HVAC has between starting and reaching operational Air Flow and Vent
Temperature
Mate
The ROM ID for the temperate sensor in the same package as the Airflow sensor
Air Flow Thresholds
Set MjU to -20
Set MnU to -10
Set MnO to a small value. Once the air flow gets to that value, the HVAC will be
considered starting.
Set MjO to a higher value. This value will be the minimum amount of airflow required to
be considered operational. An alarm will trigger if this threshold is not passed by the
HVAC Start Time expires.
Temperature Thresholds
For a cooling HVAC, the vent temperature should reach between Cooling Under and
Cooling Over.
For a warming HVAC, the vent temperature should reach between Heating Under and
Heating Over.
An alarm will trigger if one of the above thresholds is not reached before HVAC Start
Time expires.