72
/
96
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-1-3
Alternative setpoint
0 … 99 bar
2.5 bar
Everybody
Customer
-
2-1-4
Alternative setpoint selection
Disabled
Disabled
Everybody
Customer
-
Time enabled
Digital input enabled
2-1-5
Alternative set-point start time
(hours)
0 … 24 h
0
Everybody
Customer
-
2-1-6
Alternative set-point start time
(minutes)
0 … 60 min
0
Everybody
Customer
-
2-1-7
Alternative set-point stop time
(hours)
0 … 24 h
0
Everybody
Customer
-
2-1-8
Alternative set-point stop time
(minutes)
0 … 60 min
0
Everybody
Customer
-
2-1-9
Additional setpoint increase
0 … 1 bar
0.3 bar
Everybody
Customer
-
2-1-10
Minimum set-point
0 … 99 bar
0 bar
Everybody
Service
-
2-1-11
Maximum set-point
0 … 99 bar
99 bar
Everybody
Service
-
10.2.2.2 Pump operating mode
Table 30:
Pump operating mode parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-2
Pumps
-
-
Everybody
Nobody
-
2-2-1
Pump operating mode
-
-
Everybody
Nobody
-
2-2-1-1
Pump 1
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-1-2
Pump 2
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-1-3
Pump 3
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-1-4
Pump 4
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Содержание Hydro-Unit Utility Line F
Страница 29: ...29 96 1 2 Fig 12 PE connection 1 Earthing terminal 2 Location of power connection ...
Страница 58: ...58 96 ...
Страница 92: ...92 96 T Tank 79 Timers 73 W Warnings 9 Warranty claims 7 ...
Страница 93: ......
Страница 94: ......
Страница 95: ......