60
/
96
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1-1-3-2
Number of base load pumps
1 … (number of pumps - number of peak-
load pumps) if pump groups = base-load
and peak-load pump control
1 … (number of pumps - number of jockey
pumps) if pump groups = jockey-pump
control
Number of pumps
Everybody
Nobody
Y
1-1-3-3
Number of peak load pumps
0 … (number of pumps - number of base
load pumps)
0
Everybody
Service
Y
1-1-4
Maximum system load
-
-
Everybody
Nobody
-
1-1-4-1
Maximum number of pumps
0 … number of all pumps
Number of all pumps
Everybody
Service
-
1-1-5
Manual-0-automatic mode
-
-
-
-
-
1-1-5-1
Manual-0-automatic mode of pumps
Internal via display
Internal via display
Everybody
Service
-
External switches
1-1-6
Fire alarm
-
-
-
-
-
1-1-6-1
Fire alarm mode
Disabled
Disabled
Everybody
Service
-
Enabled
1-1-7
External On/Off
-
-
-
-
-
1-1-7-1
External On/Off mode
Disabled
Disabled
Everybody
Service
-
Enabled
1-1-8
Membrane rupture detection
-
-
-
-
-
1-1-8-1
Membrane rupture detection
Disabled
Disabled
Everybody
Service
-
Enabled
1-1-8-2
Digital input
-
-
Everybody
Nobody
-
1-1-8-3
Source
Water detection integrated
Water-detection on-
board
Everybody
Service
-
Membrane rupture detection by external
device
1-1-8-4
Delay time membrane rupture
detection
0 … 99 s
10 s
Everybody
Service
-
1-1-8-5
Delay time reset
0 … 99 s
2 s
Everybody
Service
-
Содержание Hydro-Unit Utility Line F
Страница 29: ...29 96 1 2 Fig 12 PE connection 1 Earthing terminal 2 Location of power connection ...
Страница 58: ...58 96 ...
Страница 92: ...92 96 T Tank 79 Timers 73 W Warnings 9 Warranty claims 7 ...
Страница 93: ......
Страница 94: ......
Страница 95: ......